Domestic cooking appliances for use by residents of Group R-2 college dormitories shall be in accordance with Sections 420.11.1 and 420.11.2.
420.11.1 Cooking Appliances
Where located in Group R-2 college dormitories, domestic cooking appliances for use by residents shall be in compliance with all of the following:
  1. The types of domestic cooking appliances shall be limited to ovens, cooktops, ranges, warmers, coffee makers and microwaves.
  2. Domestic cooking appliances shall be limited to approved locations.
  3. Cooktops and ranges shall be protected in accordance with Section 904.14.
  4. Cooktops and ranges shall be provided with a domestic cooking hood installed and constructed in accordance with Section 505 of the International Mechanical Code.
420.11.2 Cooking Appliances in Sleeping Rooms
Cooktops, ranges and ovens shall not be installed or used in sleeping rooms.