[F] 907.2.8 Group R-1
JUMP TO FULL CODE CHAPTER
Fire alarm systems and smoke alarms shall be installed in Group R-1 occupancies as required in Sections 907.2.8.1 through 907.2.8.3.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group R-1 occupancies.
Exceptions:
- A manual fire alarm system is not required in buildings not more than two stories in height where all individual sleeping units and contiguous attic and crawl spaces to those units are separated from each other and public or common areas by not less than 1-hour fire partitions and each individual sleeping unit has an exit directly to a public way, egress court or yard.
- Manual fire alarm boxes are not required throughout the building where all of the following conditions are met:
- The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
- The notification appliances will activate upon sprinkler water flow.
- Not fewer than one manual fire alarm box is installed at an approved location.
An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed throughout all interior corridors serving sleeping units.
Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
Single- and multiple-station smoke alarms shall be installed in accordance with Section 907.2.10.
Related Code Sections
1107.6.1 Accessibility, Group R-1
Accessible units and Type B units shall be provided in Group R-1 occupancies in accordance with Sections 1107.6.1.1 and 1107.6.1.2 ...
Building Code 2018 of Illinois > 11 Accessibility > 1107 Dwelling Units and Sleeping Units > 1107.6 Group R > 1107.6.1 Group R-1
803.4.1.5 Alterations—Level 2, Group R-1
A fire alarm system shall be installed in Group R-1 occupancies as required by the International Fire Code for existing Group R-1 occupancies ...
Existing Building Code 2018 of Illinois > 8 Alterations—Level 2 > 803 Fire Protection > 803.4 Fire Alarm and Detection > 803.4.1 Occupancy Requirements > 803.4.1.5 Group R-1
907.2.10.1 Fire Protection and Life Safety Systems, Group R-1
Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1: In sleeping areas. In every room ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.10 Single- And Multiple-Station Smoke Alarms > 907.2.10.1 Group R-1
1103.2.11 Accessibility, Residential Group R-1
Buildings of Group R-1 containing not more than five sleeping units for rent or hire that are also occupied as the residence of the proprietor ...
Building Code 2018 of Illinois > 11 Accessibility > 1103 Scoping Requirements > 1103.2 General Exceptions > 1103.2.11 Residential Group R-1
310.2 Occupancy Classification and Use, Residential Group R-1
Residential Group R-1 occupancies containing sleeping units where the occupants are primarily transient in nature, including: Boarding houses ...
Building Code 2018 of Illinois > 3 Occupancy Classification and Use > 310 Residential Group R > 310.2 Residential Group R-1