• Codes
  • Features
  • Pricing
  • Sign Up
  • Log in
Log in
Sign Up
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Contact
  • Terms
  • Privacy
// CODE SNIPPET

Section 453 Group L [Sfm]

California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 453 Group L [Sfm]
JUMP TO FULL CODE CHAPTER

453.1 Scope

The provisions of this section shall apply to buildings or structures, or portions thereof, containing one or more Group L laboratory suites as defined in Section 453.2.

453.2 Definitions

The following terms are defined in Chapter 2:

LABORATORY SUITE.

[F] LIQUID TIGHT FLOOR.

453.3 Laboratory suite requirements

453.3.1

The gross square footage of an individual laboratory suite shall not exceed 10,000 sq ft (929 m2).

453.3.2

An individual laboratory suite shall not serve more than a single tenant.

Exception: A laboratory suite controlled by a single responsible party.

453.4 Construction

453.4.1 Separation of laboratory suites

453.4.1.1

Laboratory suites shall be separated from other occupancies in accordance with Table 508.4.

453.4.1.2

Laboratory suites shall be separated from other laboratory suites by a fire barrier having a fire-resistance rating of not less than 1-hour.

453.4.1.3

Laboratory suites shall be separated from control areas by a minimum 2-hour fire-resistance rating in accordance with Sections 707 and 711.

Exception: Laboratory suites shall be separated from control areas by a minimum 1-hour fire-resistance rating on floor levels below the 4th story.

453.4.1.4 Horizontal separation

The floor construction of the laboratory suite and the construction supporting the floor of the laboratory suite shall have a minimum 2-hour fire-resistance rating in accordance with Section 711.

Exceptions:

  1. The floor construction of the laboratory suite and the construction supporting the floor of the laboratory suite are allowed to be 1-hour fire-resistance rated in buildings of Type IIA, IIIA and VA construction.
  2. When an individual laboratory suite occupies more than one story, the intermediate floors contained within the suite shall comply with the requirements of Table 601.

453.4.2 Structural design occupancy category

453.4.2.1

Buildings containing Group L occupancies with an occupant load greater than 500 for colleges or adult education facilities, or other buildings with an occupant load greater than 5,000 shall be classified as Occupancy Category III in accordance with Chapters 16 and 16A.

453.4.2.2

Other buildings containing Group L occupancies shall be classified as Occupancy Category II in accordance with Chapters 16 and 16A.

453.4.3 Fire barrier and fire-smoke barrier

453.4.3.1 Fire barrier

A fire barrier having a fire resistance rating of not less than 2-hours shall divide any story containing more than one laboratory suite above the 4th story.

453.4.3.1.1

Fire barriers shall be continuous from exterior wall to exterior wall,

453.4.3.1.2

The fire barrier shall divide the floor so that the square footage on each side of the 2-hour fire barrier is not less than 30 percent of the total floor area, and

453.4.3.1.3

The number of laboratory suites on each side of the 2-hour fire barrier shall not be less than 25 percent of the total number of laboratory suites on the floor.

453.4.3.2 Fire-smoke barrier

Any story containing a Group L occupancy above the 10th story shall be subdivided by a fire-smoke barrier constructed as a fire barrier having a fire resistance rating of not less than 2-hours and shall also comply with the smoke barrier requirements of Section 709.

The 2-hour fire- smoke barrier shall be in accordance with Sections 453.4.3 through 453.4.3.2.3.

453.4.3.2.1

A minimum of one door opening shall be provided in the 2-hour fire-smoke barrier for emergency access.

453.4.3.2.2

Each side of the 2-hour fire- smoke barrier shall be designed as a separate smoke zone designed in accordance with Section 909.6.

453.4.3.2.3

The area on each side of the 2-hour fire-smoke barrier shall be served by a minimum of one exit enclosure in accordance with Section 1022.

453.4.4 Emergency response equipment area

An area for emergency response equipment shall be provided on each floor in an approved location. The area shall be a minimum of 50 square feet (4.6 m2), accessed from outside the laboratory suite and identified with signage

453.4.5 Liquid tight floor

All portions of the laboratory suite where hazardous materials may be present shall be provided with a liquid tight floor. Where the floor is designed to provide spill control or secondary containment the floor shall be designed in accordance with California Fire Code Section 5004.2.

453.4.6 Emergency power

An emergency power system shall be provided in accordance with Chapter 27.

453.4.6.1 Required systems

Emergency power shall be provided for all electrically operated equipment, systems and connected control circuits including:

  1. Mechanical ventilation systems. See Section 453.4.7.2.
  2. Emergency alarm and monitoring systems.
  3. Temperature control systems required to prevent unsafe process excursions or chemical reactions.
  4. Treatment systems and scrubbers.
  5. Egress lighting.
  6. Electrically operated systems required elsewhere in this code and the California Fire Code.

453.4.7 Ventilation

453.4.7.1 Compatibility

Incompatible materials shall not be conveyed in the same duct system. Combined products in mechanical exhaust ducts shall not create a physical hazard or reaction that could degrade the duct material. The building official may require a technical report in accordance with Section 453.7.1.

453.4.7.2 Fire dampers, smoke dampers and combination fire/smoke dampers

Fire dampers, smoke dampers or fire/smoke dampers shall not be permitted in product conveying and other mechanical exhaust duct systems used to maintain a safe laboratory environment. When the exhaust duct penetrates the laboratory suite boundary the exhaust duct shall be located within a horizontal assembly having a fire resistance rating equal to the fire barrier.

453.4.7.3 Duct materials

Product conveying and other mechanical exhaust duct systems used to maintain a safe laboratory environment shall be constructed in accordance with Chapters 5 and 6 of the California Mechanical Code.

453.4.7.4 Laboratory suite exhaust air

453.4.7.4.1

Exhaust air from laboratory suites shall not be recirculated.

453.4.7.4.2

Laboratory suite exhaust air shall be independently ducted to a point outside the building or a roof top structure.

Exceptions:

  1. Exhaust ducts serving a single laboratory suite.
  2. Exhaust ducts serving separate laboratory suites on the same story may be connected to a common duct within a fire rated vertical shaft when the sub-duct extends vertically upward at least 22 inches.
  3. Exhaust ducts serving separate laboratory suites on the basement through the 4th story may be connected to a common duct within a fire rated vertical shaft when the sub-duct extends vertically upward at least 22 inches.
  4. Exhaust ducts serving separate laboratory suites on the 5th story and above may be connected to a common duct that does not exceed 100 vertical feet within a fire rated vertical shaft when the subducts extends vertically upward at least 22 inches. Ducts serving the 5th story and above shall be separate from the duct serving the 4th story and below, but may be within the same fire rated shaft.

453.4.7.4.3

Laboratory suite exhaust ducts shall not penetrate the 2-hour fire barrier required by Section 453.4.3.

Exception: Where the exhaust duct is enclosed in a 2-hour shaft in accordance with Section 708.

453.4.7.5 Ventilation rates

Mechanical exhaust ventilation systems shall provide a minimum ventilation rate not less than 1 cubic feet per minute per square foot [0.00508 m3/(s•m2)] of floor area, or 6 air exchanges per hour, whichever is greater. Systems shall operate continuously at the designed ventilation rate.

453.4.7.6 Mechanical ventilation systems on emergency power

When operating on emergency power, the ventilation rate may be reduced to a level sufficient to maintain a differential pressure negative to the surrounding area.

453.4.7.7 Mechanical ventilation system balancing

Mechanical ventilation systems shall be designed and balanced such that during normal and emergency conditions the door opening forces comply with the requirements of Sections 1008.1.3 and Chapter 11B as applicable. Emergency conditions shall include: supply fan shutdown or failure, closing of smoke dampers or combination fire/smoke dampers, or emergency power.

453.5 Fire protection systems

453.6 Means of egress

453.6.1 Access to exits

Every portion of a laboratory suite containing hazardous materials and having a floor area of 500 square feet (19 m2) or more shall have access to not less than two separate exits or exit-access doorways in accordance with Section 1015.2.

453.6.2 Door swing

All exit and exit-access doors serving areas with hazardous materials shall swing in the direction of exit travel, regardless of the occupant load served.

453.6.3 Panic hardware

Exit and exit access doors from areas with hazardous materials shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.

453.6.4 Buildings more than four stories

A minimum of one exit shall be provided to serve the floor on each side of the 2-hour fire barrier and shall comply with the provisions of Chapter 10.

453.6.5 Corridors

Corridors shall comply with Section 1018 and shall have opening protection in accordance with Tables 716.5 and 716.6.

453.7 Hazardous materials

453.7.1 Technical report

The enforcing agency may require a technical opinion and report to identify and develop methods of protection from the hazards presented by the hazardous materials. A qualified person, firm or corporation, approved by the enforcing agency, shall prepare the opinion and report, and shall be provided without charge to the enforcing agency. The opinion and report may include, but is not limited to, the preparation of a hazardous material management plan (HMMP); chemical analysis; recommendations for methods of isolation, separation, containment or protection of hazardous materials or processes, including appropriate engineering controls to be applied; the extent of changes in the hazardous behavior to be anticipated under conditions of exposure to fire or from hazard control procedures; and the limitations or conditions of use necessary to achieve and maintain control of the hazardous materials or operations. The report shall be entered into the files of the code enforcement agencies. Proprietary and trade secret information shall be protected under the laws of the state or jurisdiction having authority.

453.7.2 Multiple hazards

When a hazardous material has multiple hazards, all hazards shall be addressed and controlled in accordance with the provisions of this code.

453.7.3 Percentage of maximum allowable quantities

The percentage of the maximum allowable quantity of hazardous materials per laboratory suite permitted for each story level within a building shall be in accordance with Table 453.7.3.1.

TABLE 453.7.3.1

HAZARDOUS MATERIALS QUANTITY PER LABORATORY SUITE

STORYPERCENTAGE OF MAXIMUM ALLOWABLE QUANTITY PER LABORATORY SUITEa, bNUMBER OF LAB SUITES PER FLOOR BASED ON CONSTRUCTION TYPE
Type IAType IBType IIA, IIIA, IVType IIB, IIIB, VAType VB
Above grade planeAbove 200NPNPNPNPNP
15 to 20254NPNPNPNP
11, 12, 13, 14508NPNPNPNP
7, 8, 9, 105016NPNPNPNP
6752020NPNPNP
4, 575202020NPNP
3100ULULULULNP
1, 2100ULULULULUL
Below grade plane175c1010101010
250d55555
3 and below0NPNPNPNPNP

UL = Unlimited, NP= Not permitted

  1. Percentages shall be of the maximum allowable quantity per laboratory suite shown in Tables 307.1(1) and 307.1(2). Allowable hazardous material increases for buildings equipped throughout with an automatic sprinkler system shall not be applicable to Group L occupancies.
  2. When an individual laboratory suite occupies more than one story, the more restrictive percentage of the maximum allowable quantity per laboratory suite shall apply.
  3. The total aggregate quantity of flammable liquids on the first story below grade shall be limited to the maximum total aggregate quantity for Group B occupancy control areas.
  4. The total aggregate quantity of flammable liquids on the second story level below grade shall be limited to a maximum total aggregate quantity for Group B occupancy control areas.

453.7.4 Handling and transportation

The handling and transportation of hazardous materials shall be in accordance with Section 5003 of the California Fire Code.

453.7.5 Transportation of hazardous materials above the 10th story

Transportation of hazardous materials above the 10th story shall be limited to 5 percent of the maximum allowable quantities of Tables 307.1 (1) and 307.1(2.) Quantities are permitted to be increased 100 percent in buildings with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Materials where footnote g of Table 307.1(1) applies shall not be increased.

453.8 Elevators and elevator lobbies above the 10th story

Any story containing a Group L occupancy above the 10th story shall be provided with elevators and elevator lobbies in accordance with Sections 453.8.1 through 453.8.3.

453.8.1

An elevator that serves every story of the building shall be provided on each side of the 2-hour fire-smoke barrier.

453.8.2

An elevator lobby shall be provided on each side of the 2-hour fire-smoke barrier at each floor in accordance with Section 3006.

453.8.3

The elevator and its associated elevator lobbies and elevator machine rooms shall be pressurized in accordance with Section 909.6.

453.9

Existing Group L (Formerly Group H-8) occupancies, additions, alterations, or repairs. See California Fire Code Chapter 11 and California Existing Building Code.

Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 453 Special Detailed Requirements Based on Use and Occupancy, Group L [Sfm]
a Group L occupancy above the 10 th story shall be provided with elevators and elevator lobbies in accordance with Sections 453.8.1 through 453.8.3 ...
California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 453 Group L [Sfm]
Section 313 Use and Occupancy Classification, Laboratories Group L [SFM]
[SFM] Group L occupancy includes the use of a building or structure, or a portion thereof, containing one or more laboratory suites as defined ...
California Building Code 2016 (Vol 1) > 3 Use and Occupancy Classification > 313 Laboratories Group L [SFM]
453.4 Special Detailed Requirements Based on Use and Occupancy, Construction
containing Group L occupancies with an occupant load greater than 500 for colleges or adult ...
California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 453 Group L [Sfm] > 453.4 Construction
453.5 Special Detailed Requirements Based on Use and Occupancy, Fire protection systems
California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 453 Group L [Sfm] > 453.5 Fire protection systems
453.6 Special Detailed Requirements Based on Use and Occupancy, Means of egress
Every portion of a laboratory suite containing hazardous materials and having a floor area of 500 square feet (19 m 2 ) or more shall have access ...
California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 453 Group L [Sfm] > 453.6 Means of egress
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US