• Codes
  • Features
  • Pricing
  • Sign Up
  • Log in
Log in
Sign Up
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Contact
  • Terms
  • Privacy
// CODE SNIPPET

Section 436 Group I-4 [Sfm]

California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 436 Group I-4 [Sfm]
JUMP TO FULL CODE CHAPTER

436.1 Group I-4 special provisions

Rooms classified as Group I-4 shall not be located above or below the first story.

Exceptions:

  1. Basements or stories having floor levels located within 4 feet (1219 mm), measured vertically, from adjacent ground level at the level of exit discharge, provided the basement or story has exterior exit doors at that level.
  2. In buildings equipped with an automatic sprinkler system throughout, rooms used for kindergarten, first- and second-grade children or for day-care purposes may be located on the second story, provided there are at least two exterior exit doors, or other egress systems complying with Section 1017 with two exits, for the exclusive use of such occupants. Egress systems for the exclusive use of such occupants shall be maintained until exit discharge at grade is attained.
  3. Group I-4 child-care facilities may be located above the first story in buildings of Type I construction and in Types II-A and III-A construction, subject to the limitation of Section 503 when:

    1. 3.1. Group I-4 childcare facilities with children under the age of seven or containing more than 12 children per story shall not be located above the fourth floor; and
    2. 3.2. The entire story in which the Group I-4 child-care facility is located is equipped with an approved manual fire alarm and smoke-detection system. (See the Fire Code.) Actuation of an initiating device shall sound an audible alarm throughout the entire story. When a building fire alarm system is required by other provisions of this code or the Fire Code, the alarm system shall be connected to the building alarm system. An approved alarm signal shall sound at an approved location in the Group I-4 child-care facility to indicate a fire alarm or sprinkler flow condition in other portions of the building; and
    3. 3.3. Group I-4 child-care facilities, if more than 1,000 square feet (92.9 m2) in area, is divided into at least two compartments of approximately the same size by a smoke barrier with door openings protected by smoke- and draft-control assemblies having a fire-protection rating of not less than 20 minutes. Smoke barriers shall have a fire-resistive rating of not less than one hour. In addition to the requirements of Section 508.3.3, occupancy separations between Group I-4 child-care and other occupancies shall be constructed as smoke barriers. Door openings in the smoke barrier shall be tightfitting, with gaskets installed as required by Section 710, and shall be automatic closing by actuation of the automatic sprinklers, fire alarm or smoke-detection system.
    4. 3.4. Each compartment formed by the smoke barrier has not less than two exits or exit access doors, one of which is permitted to pass through the adjoining compartment; and
    5. 3.5. Where two or more exits or exit access are required at least one shall not share a common path of travel.
    6. 3.6. The building is equipped with an automatic sprinkler system throughout.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 436 Special Detailed Requirements Based on Use and Occupancy, Group I-4 [Sfm]
Rooms classified as Group I-4 shall not be located above or below the first story. Exceptions: Basements or stories having floor levels ...
California Building Code 2016 (Vol 1) > 4 Special Detailed Requirements Based on Use and Occupancy > 436 Group I-4 [Sfm]
Section 436 Appendix Chapter 4 Special Detailed Requirements Based on Use and Occupancy, Group I-4 [Sfm]
Rooms classified as Group I-4 shall not be located above or below the first story. Exceptions: Basements or stories having floor levels located ...
California Fire Code 2016 > Occupancy Appendix Chapter 4 Special Detailed Requirements Based on Use and Occupancy > 436 Group I-4 [Sfm]
Section 302 Use and Occupancy Classification, Classification
Section 307): Groups H-1, H-2, H-3, H-4 and H-5 Institutional (see Section 308): Groups I-1, I-2, I-2.1, I-3 and I-4 [SFM] Laboratory (see ...
California Building Code 2016 (Vol 1) > 3 Use and Occupancy Classification > 302 Classification
305.2 Use and Occupancy Classification, Group E, day care facilities
as Group I-4. Rooms and spaces within places ...
California Building Code 2016 (Vol 1) > 3 Use and Occupancy Classification > 305 Educational Group E > 305.2 Group E, day care facilities
Section 1115 Construction Requirements for Existing Buildings, Existing Group I Occupancies [Sfm]
wall and ceiling finishes shall conform to the requirements for a Group R-1 Occupancy as specified in Chapter 8 of the California Building Code ...
California Fire Code 2016 > 11 Construction Requirements for Existing Buildings > 1115 Existing Group I Occupancies [Sfm]
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US