907.2.6.1 Group I-1
JUMP TO FULL CODE CHAPTER
An automatic smoke detection system shall be installed in corridors, waiting areas open to corridors and habitable spaces other than sleeping units and kitchens. The system shall be activated in accordance with Section 907.5.
Exception: Smoke detection is not required for exterior balconies.
Smoke detectors and notification appliances shall be installed in dwelling units and such notification appliances shall activate only in the unit in which the alarm originates. Such detectors and appliances shall be annunciated by a dwelling unit at a constantly attended location from which the fire alarm system is capable of being manually activated. Smoke detectors are required in the following areas:
- Sleeping areas;
- Every room in the path of the means of egress from the sleeping area to the door leading from the dwelling unit;
- Each story within the unit, including below-grade stories. For dwelling units with split levels and without an intervening door between the adjacent levels, a smoke detector installed on the upper level shall suffice for the adjacent lower level.
Related Code Sections
1107.5.1 Accessibility, Group I-1
Group I-1 occupancies shall be provided with accessible features in accordance with Section 1107.5.1.1 ...
NYC Building Code 2008 > 11 Accessibility > 1107 Dwelling Units and Sleeping Units > 1107.5 Group I > 1107.5.1 Group I-1
308.2 Use and Occupancy Classification, Group I-1
to persons capable of self-preservation, in the same building, shall be classified as Group I-1.
Exception: Such a facility offering supervised care ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 308 Institutional Group I > 308.2 Group I-1
308.2 Use and Occupancy Classification, Group I-1
offering care on a 24-hour basis to persons capable of self-preservation, in the same building, shall be classified as Group I-1. Exception: Such ...
NYC Building Code 2014 > 3 Use and Occupancy Classification > 308 Institutional Group I > 308.2 Group I-1
907.2.6.1 Fire Protection Systems, Group I-1
An automatic smoke detection system shall be installed in corridors, waiting areas open to corridors and habitable spaces other than sleeping units ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.6 Group I > 907.2.6.1 Group I-1
1107.5.1 Accessibility, Group I-1 Accessible Units
In Group I-1 occupancies, at least ten percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units. The ...
NYC Building Code 2014 > 11 Accessibility > 1107 Dwelling Units and Sleeping Units > 1107.5 Group I > 1107.5.1 Group I-1 Accessible Units