[F] 415.6.1.1 Group H-1
Related Code Sections
415.6.1.1 Special Detailed Requirements Based on Occupancy and Use, Group H-1
Group H-1 occupancies shall be set back not less than 75 feet (22 860 mm) and not less than required by the International Fire Code . Exception ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.6 Fire Separation Distance > 415.6.1 Group H Occupancy Minimum Fire Separation Distance > 415.6.1.1 Group H-1
415.6.4.1 Special Detailed Requirements Based on Occupancy and Use, Group H-1
Group H-1 occupancies shall be set back not less than 75 feet (22 860 mm) and not less than required by the International Fire Code . Exception ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.6 Fire Separation Distance > 415.6.4 Group H Occupancy Minimum Fire Separation Distance > 415.6.4.1 Group H-1
307.3 Occupancy Classification and Use, High-Hazard Group H-1
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include ...
Building Code 2021 of Illinois > 3 Occupancy Classification and Use > 307 High-Hazard Group H > 307.3 High-Hazard Group H-1
307.3 Occupancy Classification and Use, High-Hazard Group H-1
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include ...
Building Code 2018 of Illinois > 3 Occupancy Classification and Use > 307 High-Hazard Group H > 307.3 High-Hazard Group H-1
307.3.1 Occupancy Classification and Use, Occupancies Containing Explosives Not Classified as H-1
and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 ...
Building Code 2018 of Illinois > 3 Occupancy Classification and Use > 307 High-Hazard Group H > 307.3 High-Hazard Group H-1 > 307.3.1 Occupancies Containing Explosives Not Classified as H-1