[F] 903.2.5 Group H
JUMP TO FULL CODE CHAPTER
Automatic sprinkler systems shall be provided in high-hazard occupancies as required in Sections 903.2.5.1 through 903.2.5.3.
An automatic sprinkler system shall be installed in Group H occupancies.
An automatic sprinkler system shall be installed throughout buildings containing Group H-5 occupancies. The design of the sprinkler system shall not be less than that required by this code for the occupancy hazard classifications in accordance with Table 903.2.5.2. Where the design area of the sprinkler system consists of a corridor protected by one row of sprinklers, the maximum number of sprinklers required to be calculated is 13.
[F] TABLE 903.2.5.2
GROUP H-5 SPRINKLER DESIGN CRITERIA
LOCATION | OCCUPANCY HAZARD CLASSIFICATION |
Fabrication areas | Ordinary Hazard Group 2 |
Service corridors | Ordinary Hazard Group 2 |
Storage rooms without dispensing | Ordinary Hazard Group 2 |
Storage rooms with dispensing | Extra Hazard Group 2 |
Corridors | Ordinary Hazard Group 2 |
An automatic sprinkler system shall be provided in buildings, or portions thereof, where cellulose nitrate film or pyroxylin plastics are manufactured, stored or handled in quantities exceeding 100 pounds (45 kg).
Related Code Sections
901.6.3 Fire Protection Systems, Group H
Supervision and monitoring of emergency alarm, detection and automatic fire-extinguishing systems in Group H occupancies shall be in accordance ...
2014 FBC - Building, 5th edition > 9 Fire Protection Systems > 901 General > 901.6 Supervisory Service > 901.6.3 Group H
901.6.3 Fire Protection Systems, Group H
Supervision and monitoring of emergency alarm, detection and automatic fire-extinguishing systems in Group H occupancies shall be in accordance ...
2017 FBC - Building, 6th edition > 9 Fire Protection Systems > 901 General > 901.6 Supervisory Service > 901.6.3 Group H
901.6.3 Fire Protection Systems, Group H
Supervision and monitoring of emergency alarm, detection and automatic fire-extinguishing systems in Group H occupancies shall be in accordance ...
2020 FBC - Building, 7th edition > 9 Fire Protection Systems > 901 General > 901.6 Supervisory Service > 901.6.3 Group H
903.2.5 Fire Protection Systems, Group H
An automatic sprinkler system shall be installed in Group H occupancies ...
2014 FBC - Building, 5th edition > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.5 Group H
903.2.5 Fire Protection Systems, Group H
An automatic sprinkler system shall be installed in Group H occupancies ...
2017 FBC - Building, 6th edition > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.5 Group H