// CODE SNIPPET
[F] 903.2.4 Group F-1
Go To Full Code Chapter
An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists:
- A Group F-1 fire area exceeds 12,000 square feet (1115 m2).
- A Group F-1 fire area is located more than three stories above grade plane.
- The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).
[F] 903.2.4.1 Woodworking Operations
An automatic sprinkler system shall be provided throughout all Group F-1 occupancy fire areas that contain woodworking operations in excess of 2,500 square feet (232 m2) in area that generate finely divided combustible waste or use finely divided combustible materials.
[F] 903.2.4.2 Group F-1 Distilled Spirits
An automatic sprinkler system shall be provided throughout a Group F-1 fire area used for the manufacture of distilled spirits.
[F] 903.2.4.3 Group F-1 Upholstered Furniture or Mattresses
An automatic sprinkler system shall be provided throughout a Group F-1 fire area that exceeds 2,500 square feet (232 m2) used for the manufacture of upholstered furniture or mattresses.
Related Code Sections
903.2.4 Fire Protection and Life Safety Systems, Group F-1
An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions ...
903.2.4 Fire Protection and Life Safety Systems, Group F-1
An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions ...
910.2.1 Fire Protection and Life Safety Systems, Group F-1 or S-1
be installed in buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 50,000 square feet (4645 m2) of undivided area ...
910.2.1 Fire Protection and Life Safety Systems, Group F-1 or S-1
be installed in buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 50,000 square feet (4645 m2) of undivided area ...
1017.2.2 Means of Egress, Groups F-1 and S-1 Increase
The maximum exit access travel distance shall be 400 feet (122 m) in Group F-1 or S-1 occupancies where all of the following conditions are met ...