908.7.2 Group E, I-2 and I-4 Occupancies
JUMP TO FULL CODE CHAPTER
Listed carbon monoxide detectors with built-in sounder bases shall be transmit a signal to a central supervising station and shall be permitted to initiate an audible and visual supervisory alarm at a constantly attended location.
- Carbon monoxide detectors with built-in sounder bases shall be installed within any room containing carbon monoxide-producing equipment.
Exception: Kitchens or laboratories. - Carbon monoxide detectors with built-in sounder bases shall be installed in corridors on the story where carbon monoxide-producing equipment unit is located, as well as one story above and one story below.
- Carbon monoxide detectors with built-in sounder bases shall be installed in all corridors on the story where enclosed parking is located, as well as one story above and one story below.
Related Code Sections
908.7.2 Fire Protection Systems, Group E, I-2 and I-4 Occupancies
equipment or enclosed parking is located. 2. Carbon monoxide detectors and audible notification appliances shall be installed within any ...
NYC Building Code 2008 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.2 Group E, I-2 and I-4 Occupancies
908.7.2 Fire Protection Systems, Group E, I-2 and I-4 Occupancies
Listed carbon monoxide detectors with built-in sounder bases shall be transmit a signal to a central supervising station and shall be permitted ...
NYC Building Code 2014 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.2 Group E, I-2 and I-4 Occupancies
804.4.1 Interior Finishes, Minimum Critical Radiant Flux
Interior floor finishes shall not be less than Class I in Occupancy Groups I-2 and I-3 and not less than Class II in Occupancy Groups A, B, E, H, I-4 ...
NYC Building Code 2014 > 8 Interior Finishes > 804 Interior Floor Finish > 804.4 Interior Floor Finish Limitations > 804.4.1 Minimum Critical Radiant Flux
804.5.1 Interior Finishes, Minimum Critical Radiant Flux
Interior floor finishes shall not be less than Class I in Occupancy Groups I-2 and I-3 and not less than Class II in Occupancy Groups A, B, E, H, I ...
NYC Building Code 2008 > 8 Interior Finishes > 804 Interior Floor Finish > 804.5 Interior Floor Finish Limitations > 804.5.1 Minimum Critical Radiant Flux
1103.2 Refrigeration, Occupancy Classification
and I-4. Public assembly occupancy shall include Occupancy Groups A-1, A-2, A-3, A-4, A-5 and E. Residential occupancy shall include Occupancy ...
NYC Mechanical Code 2014 > 11 Refrigeration > 1103 Refrigeration System Classification > 1103.2 Occupancy Classification