903.2.2 Group B Ambulatory Care Facilities
JUMP TO FULL CODE CHAPTER
An automatic sprinkler system shall be installed throughout all fire areas containing a Group B ambulatory care facility occupancy when either of the following conditions exists at any time:
- Four or more care recipients are incapable of self-preservation whether rendered incapable by staff or staff has accepted responsibility for care recipients already incapable.
- One or more care recipients who are incapable of self-preservation are located at other than the level of exit discharge serving such an occupancy.
In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor where such care is provided as well as all floors below, and all floors between the level of ambulatory care and the nearest level of exit discharge, including the level of exit discharge.
Related Code Sections
903.2.2 Fire Protection Systems, Group B Ambulatory Care Facilities
An automatic sprinkler system shall be installed throughout all fire areas containing a Group B ambulatory care facility occupancy when either ...
Ohio Building Code 2011 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.2 Group B Ambulatory Care Facilities
914.11 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, Group B Ambulatory Health Care Facilities
Occupancies classified as Group B ambulatory health care facilities shall comply with paragraphs (N)(11)(a)(914.11.1) to (N)(11)(c)(914.11.3 ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 914 Fire Protection Based on Special Detailed Requirements of Use and Occupancy > 914.11 Group B Ambulatory Health Care Facilities
903.2.2 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, Group B Ambulatory Health Care Facilities
An automatic sprinkler system shall be installed throughout all fire areas containing a Group B ambulatory health care facility occupancy when either ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.2 Group B Ambulatory Health Care Facilities
907.2.2.1 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, Group B—Ambulatory Health Care Facilities
Fire areas containing Group B ambulatory health care facilities shall be provided with an electronically supervised automatic smoke detection system ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required-New Buildings and Structures > 907.2.2 Group B > 907.2.2.1 Group B—Ambulatory Health Care Facilities
422.1 Special Detailed Requirements Based on Use and Occupancy, General
Occupancies classified as Group B ambulatory care facilities shall comply with the provisions of Sections 422.1 through 422.7 and other applicable ...
Ohio Building Code 2011 > 4 Special Detailed Requirements Based on Use and Occupancy > 422 Ambulatory Care Facilities > 422.1 General