507.6 Group A Buildings
JUMP TO FULL CODE CHAPTER
The area of a Group A-1, A-2, A-3, or A-4 building of Type IIA, IIIA or IV construction shall not be limited where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The area of a one-story, Group A-3 building used as a house of worship, community hall, dance hall, exhibition hall, gymnasium, lecture hall, indoor swimming pool or tennis court of Type IIB construction shall not be limited when all of the following criteria are met:
- The building shall not have a stage other than a platform.
- The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
- The assembly floor shall be located at or within 21 inches (533 mm) of street or grade level and all exits are provided with ramps complying with Section 1010.1 to the street or grade level.
- The building shall be surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
Related Code Sections
507.5 General Building Heights and Areas; Separation of Occupancies, Group A Buildings
The area of a Group A-1, A-2, A-3, or A-4 building of Type IIA, IIIA, or IV construction shall not be limited where the building is equipped ...
NYC Building Code 2008 > 5 General Building Heights and Areas; Separation of Occupancies > 507 Unlimited Area Buildings > 507.5 Group A Buildings
507.6 General Building Heights and Areas; Separation of Occupancies, Group A Buildings
The area of a Group A-1, A-2, A-3, or A-4 building of Type IIA, IIIA or IV construction shall not be limited where the building is equipped ...
NYC Building Code 2014 > 5 General Building Heights and Areas; Separation of Occupancies > 507 Unlimited Area Buildings > 507.6 Group A Buildings
905.3.2 Fire Protection Systems, Group A
Class I automatic wet standpipes shall be provided in nonsprinklered Group A buildings having an occupant load exceeding 1,000 persons ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.2 Group A
905.3.2 Fire Protection Systems, Group A
Class I automatic wet standpipes shall be provided in nonsprinklered Group A buildings having an occupant load exceeding 1,000 persons ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.2 Group A
3003.3.4 Elevators and Conveying Systems, Other Elevator Cars
In high-rise buildings classified in Occupancy Groups A, B, E, F, H, I, M and S, in low-rise buildings classified in Occupancy Group B with a gross ...
NYC Building Code 2014 > 30 Elevators and Conveying Systems > 3003 Elevator Emergency Operations > 3003.3 Elevator in Readiness > 3003.3.4 Other Elevator Cars