An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
  1. The fire area exceeds 12,000 square feet (1115 m2).
  2. The fire area has an occupant load of 300 or more.
  3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.