An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
  1. The fire area exceeds 5,000 square feet (464 m2).
  2. The fire area has an occupant load of 100 or more.
  3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.

Related Code Sections

903.2.1.2 Fire Protection and Life Safety Systems, Group A-2
An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 ...
903.2.1.2 Fire Protection and Life Safety Systems, Group A-2
An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 ...
303.3 Occupancy Classification and Use, Assembly Group A-2
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Casinos (gaming ...
303.3 Occupancy Classification and Use, Assembly Group A-2
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Casinos (gaming ...
905.5.1 Fire Protection and Life Safety Systems, Groups A-1 and A-2
In Group A-1 and A-2 occupancies having occupant loads exceeding 1,000 persons, hose connections shall be located on each side of any stage, on each ...