(B) Grounding-Pole Identification
Go To Full Code Chapter
Grounding-type receptacles, adapters, cord connections, and attachment plugs shall have a means for connection of an equipment grounding conductor to the grounding pole.
- A green-colored hexagonal-headed or -shaped terminal screw or nut, not readily removable.
- A green-colored pressure wire connector body (a wire barrel).
- A similar green-colored connection device, in the case of adapters. The grounding terminal of a grounding adapter shall be a green-colored rigid ear, lug, or similar device. The equipment grounding connection shall be so designed that it cannot make contact with current-carrying parts of the receptacle, adapter, or attachment plug. The adapter shall be polarized.
- If the terminal for the equipment grounding conductor is not visible, the conductor entrance hole shall be marked with the word green or ground, the letters G or GR, a grounding symbol, or otherwise identified by a distinctive green color. If the terminal for the equipment grounding conductor is readily removable, the area adjacent to the terminal shall be similarly marked.
Informational Note: See Informational Note Figure 406.10(B)(4).
Related Code Sections
(B) Equipment for General Use, Grounding-Pole Identification
to the grounding pole. A terminal for connection to the grounding pole shall be designated by one of the following: A green-colored hexagonal ...
200.10 Wiring and Protection, Identification of Terminals
to the grounded conductor is clearly evident. Exception: Terminal identification shall not be required for devices that have a normal current rating of over 30 ...
(C) Special Equipment, Grounding Pole
The electric vehicle coupler shall be provided with a grounding pole, unless provided as part of a listed isolated electric vehicle supply equipment ...
(D) Special Equipment, Grounding Pole Requirements
If a grounding pole is provided, the electric vehicle coupler shall be so designed that the grounding pole connection is the first to make ...
1806.3.4 Soils and Foundations, Increase for Poles
Isolated poles for uses such as flagpoles or signs and poles used to support buildings that are not adversely affected by a 1/2-inch (12.7 mm) motion ...