250.188 Grounding of Systems Supplying Portable or Mobile Equipment
Go To Full Code Chapter
Systems supplying portable or mobile equipment over 1000 volts, other than substations installed on a temporary basis, shall comply with 250.188(A) through (F).
(A) Portable or Mobile Equipment
Portable or mobile equipment over 1000 volts shall be supplied from a system having its neutral conductor grounded through an impedance. Where a delta-connected system over 1000 volts is used to supply portable or mobile equipment, a system neutral point and associated neutral conductor shall be derived.
(B) Exposed Non—Current-Carrying Metal Parts
(C) Ground-Fault Current
(D) Ground-Fault Detection and Relaying
Ground-fault detection and relaying shall be provided to automatically de-energize any component of a system over 1000 volts that has developed a ground fault. The continuity of the equipment grounding conductor shall be continuously monitored so as to automatically de-energize the circuit of the system over 1000 volts to the portable or mobile equipment upon loss of continuity of the equipment grounding conductor.
(E) Isolation
The grounding electrode to which the portable or mobile equipment system neutral impedance is connected shall be isolated from and separated in the ground by at least 6.0 m (20 ft) from any other system or equipment grounding electrode, and there shall be no direct connection between the grounding electrodes, such as buried pipe and fence, and so forth.
Related Code Sections
250.188 Wiring and Protection, Grounding of Systems Supplying Portable or Mobile Equipment
Systems supplying portable or mobile equipment over 1000 volts, other than substations installed on a temporary basis, shall comply with 250.188(A ...
250.188 Wiring and Protection, Grounding of Systems Supplying Portable or Mobile Equipment
Systems supplying portable or mobile equipment over 1000 volts, other than substations installed on a temporary basis, shall comply with 250.188(A ...
(B) Wiring and Protection, Exposed Non—Current-Carrying Metal Parts
Exposed non—current-carrying metal parts of portable or mobile equipment shall be connected by an equipment grounding conductor to the point at which ...
(F) Wiring and Protection, Trailing Cable and Couplers
Trailing cable and couplers of systems over 1000 volts for interconnection of portable or mobile equipment shall meet the requirements of Part III ...
(F) Wiring and Protection, Trailing Cable and Couplers
Trailing cable and couplers of systems over 1000 volts for interconnection of portable or mobile equipment shall meet the requirements of Part III ...