1803.5.4 Ground-Water Table
JUMP TO FULL CODE CHAPTER
A subsurface soil investigation shall be performed to determine whether the existing ground-water table is above or within 5 feet (1524 mm) below the elevation of the lowest floor level where such floor is located below the finished ground level adjacent to the foundation.
Exception:
A subsurface soil investigation to determine the location of the ground-water table shall not be required where waterproofing is provided in accordance with Section 1805.
Related Code Sections
1802.2.3 Soils and Foundations, Ground-Water Table
A subsurface soil investigation shall be performed to determine whether the existing ground-water table is above or within 5 feet (1524 mm) below ...
2010 Building Code of NY > 18 Soils and Foundations > 1802 Foundation and Soils Investigations > 1802.2 Where Required > 1802.2.3 Ground-Water Table
1803.5.4 Soils and Foundations, Ground-Water Table
A subsurface soil investigation shall be performed to determine whether the existing ground-water table is above or within 5 feet (1524 mm) below ...
Building Code 2015 of New York State > 18 Soils and Foundations > 1803 Geotechnical Investigations > 1803.5 Investigated Conditions > 1803.5.4 Ground-Water Table
1803.5.4 Soils and Foundations, Ground Water Table
A subsurface soil investigation shall be performed to determine whether the existing ground water table is above or within 5 feet (1524 mm) below ...
2020 Building Code of New York State > 18 Soils and Foundations > 1803 Geotechnical Investigations > 1803.5 Investigated Conditions > 1803.5.4 Ground Water Table
1805.1.3 Soils and Foundations, Ground-Water Control
Where the ground-water table is lowered and maintained at an elevation not less than 6 inches (152 mm) below the bottom of the lowest floor ...
Building Code 2015 of New York State > 18 Soils and Foundations > 1805 Dampproofing and Waterproofing > 1805.1 General > 1805.1.3 Ground-Water Control
1805.1.3 Soils and Foundations, Ground Water Control
Where the ground water table is lowered and maintained at an elevation not less than 6 inches (152 mm) below the bottom of the lowest floor ...
2020 Building Code of New York State > 18 Soils and Foundations > 1805 Dampproofing and Waterproofing > 1805.1 General > 1805.1.3 Ground Water Control