Section M2105 Ground-Source Heat-Pump System Loop Piping
Go To Full Code Chapter
M2105.1 Plastic Ground-Source Heat-Pump Loop Piping
Plastic piping and tubing material used in water-based ground-source heat-pump ground-loop systems shall conform to the standards specified in this section.
M2105.2 Used Materials
Reused pipe, fittings, valves, and other materials shall not be used in ground-source heat-pump loop systems.
M2105.3 Material Rating
Pipe and tubing shall be rated for the operating temperature and pressure of the ground-source heat-pump loop system. Fittings shall be suitable for the pressure applications and recommended by the manufacturer for installation with the pipe and tubing material installed. Where used underground, materials shall be suitable for burial.
M2105.4 Piping and Tubing Materials Standards
Ground-source heat-pump ground-loop pipe and tubing shall conform to the standards listed in Table M2105.4.
TABLE M2105.4
GROUND-SOURCE LOOP PIPEMATERIAL | STANDARD |
Chlorinated polyvinyl chloride (CPVC) | ASTM D2846; ASTM F437; ASTM F438; ASTM F439;
ASTM F441; ASTM F442; CSA B137.6
|
Cross-linked polyethylene (PEX) | ASTM F876; CSA B137.5; ANSI/CSA/IGSHPA C448; NSF 358-3 |
High-density polyethylene (HDPE) | ASTM D2737; ASTM D3035; ASTM F714;
AWWA C901; CSA B137.1; ANSI/CSA/IGSHPA C448; NSF 358-1
|
Polyethylene/aluminum/polyethylene (PE-AL-PE) pressure pipe | ASTM F1282; AWWA C903; CSA B137.9 |
Polypropylene (PP-R) | ASTM F2389; CSA B137.11; NSF 358-2 |
Polyvinyl chloride (PVC) | ASTM D1785; ASTM D2241; CSA B137.3 |
Raised temperature polyethylene (PE-RT) | ASTM F2623; ASTM F2769; CSA B137.18; ANSI/CSA/IGSHPA C448; NSF 358-4 |
M2105.5 Fittings
Ground-source heat-pump pipe fittings shall be approved for installation with the piping materials to be installed, shall conform to the standards listed in Table M2105.5 and, where installed underground, shall be suitable for burial.
TABLE M2105.5
GROUND-SOURCE LOOP PIPE FITTINGS
PIPE MATERIAL | STANDARD |
Chlorinated polyvinyl chloride (CPVC) | ASTM D2846; ASTM F437; ASTM F438; ASTM F439; ASTM F1970; CSA B137.6 |
Cross-linked polyethylene (PEX) | ASTM F877; ASTM F1807; ASTM F1960; ASTM F2080; ASTM F2159; ASTM F2434; CSA B137.5; ANSI/CSA/IGSHPA C448; NSF 358-3 |
High-density polyethylene (HDPE) | ASTM D2683; ASTM D3261; ASTM F1055; CSA B137.1; ANSI/CSA/IGSHPA C448; NSF 358-1 |
Polyethylene/aluminum/polyethylene (PE-AL-PE) | ASTM F1282; ASTM F2434; CSA B137.9 |
Polypropylene (PP-R) | ASTM F2389; CSA B137.11; NSF 358-2 |
Polyvinyl chloride (PVC) | ASTM D2464; ASTM D2466; ASTM D2467; ASTM F1970; CSA B137.2; CSA B137.3 |
Raised temperature polyethylene (PE-RT) | ASTM D2683; ASTM D3261; ASTM F1055; ASTM F1807; ASTM F2098; ASTM F2159; ASTM F2735; ASTM F2769; CSA B137.1; CSA B137.18; ANSI/CSA/IGSHPA C448; NSF 358-4 |
M2105.6 Joints and Connections
M2105.6.1 Joints Between Different Piping Materials
Joints between different piping materials shall be made with approved transition fittings.
M2105.7 Preparation of Pipe Ends
Pipe shall be cut square and shall be free of burrs and obstructions. Pipe ends shall have full-bore openings and shall be prepared in accordance with the pipe manufacturer's instructions.
M2105.8 Joint Preparation and Installation
M2105.8.1 Mechanical Joints
Mechanical joints shall be installed in accordance with the manufacturer's instructions.
M2105.8.2 Thermoplastic-Welded Joints
Joint surfaces for thermoplastic-welded joints shall be cleaned by an approved procedure. Joints shall be welded in accordance with the manufacturer's instructions.
M2105.9 CPVC Plastic Pipe
Joints between CPVC plastic pipe or fittings shall be solvent-cemented in accordance with Section P2906.9.1.2. Threaded joints between fittings and CPVC plastic pipe shall be in accordance with Section M2105.9.1.
M2105.9.1 Threaded Joints
Threads shall conform to ASME B1.20.1. The pipe shall be Schedule 80 or heavier plastic pipe and shall be threaded with dies specifically designed for plastic pipe. Thread lubricant, pipe-joint compound or tape shall be applied on the male threads only and shall be approved for application on the piping material.
M2105.10 Cross-Linked Polyethylene (PEX) Plastic Tubing
Joints between cross-linked polyethylene plastic tubing and fittings shall comply with Sections M2105.10.1 and M2105.10.2. Mechanical joints shall comply with Section M2105.8.1.
M2105.10.1 Compression-Type Fittings
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
M2105.10.2 Plastic-to-Metal Connections
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to plastic pipe or tubing.
M2105.11 Polyethylene Plastic Pipe and Tubing
Joints between polyethylene plastic pipe and tubing or fittings for ground-source heat-pump loop systems shall be heat-fusion joints complying with Section M2105.11.1, electrofusion joints complying with Section M2105.11.2, or stab-type insertion joints complying with Section M2105.11.3.
M2105.11.1 Heat-Fusion Joints
Joints shall be of the socket-fusion, saddle-fusion or butt-fusion type, and joined in accordance with ASTM D2657. Joint surfaces shall be clean and free from moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall remain undisturbed until cool. Fittings shall be manufactured in accordance with ASTM D2683 or ASTM D3261.
M2105.11.2 Electrofusion Joints
Joints shall be of the electrofusion type. Joint surfaces shall be clean and free from moisture, and scoured to expose virgin resin. Joint surfaces shall be heated to melt temperatures for the period of time specified by the manufacturer. The joint shall remain undisturbed until cool. Fittings shall be manufactured in accordance with ASTM F1055.
M2105.11.3 Stab-Type Insert Fittings
Joint surfaces shall be clean and free from moisture. Pipe ends shall be chamfered and inserted into the fittings to full depth. Fittings shall be manufactured in accordance with ASTM F1924.
M2105.12 Polypropylene (PP) Plastic
Joints between PP plastic pipe and fittings shall comply with Sections M2105.12.1 and M2105.12.2.
M2105.12.1 Heat-Fusion Joints
Heat-fusion joints for polypropylene (PP) pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, electrofusion polypropylene fittings or by butt fusion. Joint surfaces shall be clean and free from moisture. The joint shall remain undisturbed until cool. Joints shall be made in accordance with ASTM F2389.
M2105.12.2 Mechanical and Compression Sleeve Joints
Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions.
M2105.13 Raised Temperature Polyethylene (PE-RT) Plastic Tubing
Joints between raised temperature polyethylene tubing and fittings shall comply with Sections M2105.13.1 through M2105.13.4. Mechanical joints shall comply with Section M2105.8.1.
M2105.13.1 Compression-Type Fittings
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
M2105.13.2 PE-RT-to-Metal Connections
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE-RT pipe or tubing.
M2105.13.3 Heat-Fusion Joints
Heat-fusion joints shall be of the socket-fusion, saddle-fusion or butt-fusion type, and shall be joined in accordance with ASTM D2657. Joint surfaces shall be clean and free from moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall remain undisturbed until cool. Fittings shall be manufactured in accordance with ASTM D2683 or ASTM D3261.
M2105.13.4 Electrofusion Joints
Joints shall be of the electrofusion type. Joint surfaces shall be clean and free from moisture and scoured to expose virgin resin. Joint surfaces shall be heated to melt temperatures for the period of time specified by the manufacturer and joined. The joint shall remain undisturbed until cool. Fittings shall be manufactured in accordance with ASTM F1055.
M2105.14 PVC Plastic Pipe
Joints between PVC plastic pipe or fittings shall be solvent-cemented in accordance with Section P2906.9.1.4. Threaded joints between fittings and PVC plastic pipe shall be in accordance with Section M2105.9.1.
M2105.15 Shutoff Valves
Shutoff valves shall be installed in ground-source loop piping systems in the locations indicated in Sections M2105.15.1 through M2105.15.6.
M2105.15.1 Heat Exchangers
Shutoff valves shall be installed on the supply and return side of a heat exchanger.
Exception: Shutoff valves shall not be required where heat exchangers are integral with a boiler or are a component of a manufacturer's boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves required by Section M2001.3.
M2105.15.2 Central Systems
Shutoff valves shall be installed on the building supply and return of a central utility system.
M2105.15.3 Pressure Vessels
Shutoff valves shall be installed on the connection to any pressure vessel.
M2105.15.4 Pressure-Reducing Valves
Shutoff valves shall be installed on both sides of a pressure-reducing valve.
M2105.15.5 Equipment and Appliances
Shutoff valves shall be installed on connections to mechanical equipment and appliances. This requirement does not apply to components of ground-source loop systems such as pumps, air separators, metering devices, and similar equipment.
M2105.15.6 Expansion Tanks
Shutoff valves shall be installed at connections to nondiaphragm-type expansion tanks.
M2105.16 Reduced Pressure
A pressure relief valve shall be installed on the low-pressure side of a hydronic piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with Section M2002.
M2105.17 Installation
Piping, valves, fittings, and connections shall be installed in accordance with the manufacturer's instructions.
M2105.18 Protection of Potable Water
Where ground-source heat-pump ground-loop systems have a connection to a potable water supply, the potable water system shall be protected from backflow in accordance with Section P2902.
M2105.19 Pipe Penetrations
Openings for pipe penetrations in walls, floors and ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building elements shall be sleeved. The annular space surrounding pipe penetrations shall be protected in accordance with Section P2606.1.
M2105.20 Clearance From Combustibles
A pipe in a ground-source heat pump piping system having an exterior surface temperature exceeding 250°F (121°C) shall have a clearance of not less than 1 inch (25 mm) from combustible materials.
M2105.21 Contact With Building Material
A ground-source heat-pump ground-loop piping system shall not be in direct contact with building materials that cause the piping or fitting material to degrade or corrode, or that interfere with the operation of the system.
M2105.22 Strains and Stresses
Piping shall be installed so as to prevent detrimental strains and stresses in the pipe. Provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement. Piping shall be installed so as to avoid structural stresses or strains within building components.
M2105.22.1 Flood Hazard
Piping located in a flood hazard area shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation.
M2105.23 Pipe Support
Pipe shall be supported in accordance with Section M2101.9.
M2105.24 Velocities
Ground-source heat-pump ground-loop systems shall be designed so that the flow velocities do not exceed the maximum flow velocity recommended by the pipe and fittings manufacturer. Flow velocities shall be controlled to reduce the possibility of water hammer.
M2105.25 Labeling and Marking
Ground-source heat-pump ground-loop system piping shall be marked with tape, metal tags or other methods where it enters a building. The marking shall state the following words: "GROUND-SOURCE HEAT-PUMP LOOP SYSTEM." The marking shall indicate if antifreeze is used in the system and shall indicate the chemicals by name and concentration.
M2105.26 Chemical Compatibility
Antifreeze and other materials used in the system shall be chemically compatible with the pipe, tubing, fittings and mechanical systems.
M2105.27 Makeup Water
The transfer fluid shall be compatible with the makeup water supplied to the system.
M2105.28 Testing
Before connection header trenches are backfilled, the assembled loop system shall be pressure tested with water at 100 psi (689 kPa) for 15 minutes without observed leaks. Flow and pressure loss testing shall be performed and the actual flow rates and pressure drops shall be compared to the calculated design values. If actual flow rate or pressure drop values differ from calculated design values by more than 10 percent, the cause shall be identified and corrective action taken.