1926.351(c) Ground Returns and Machine Grounding
JUMP TO FULL CODE CHAPTER
A ground return cable shall have a safe current carrying capacity equal to or exceeding the specified maximum output capacity of the arc welding or cutting unit which it services. When a single ground return cable services more than one unit, its safe current-carrying capacity shall equal or exceed the total specified maximum output capacities of all the units which it services.
Pipelines containing gases or flammable liquids, or conduits containing electrical circuits, shall not be used as a ground return. For welding on natural gas pipelines, the technical portions of regulations issued by the Department of Transportation, Office of Pipeline Safety, 49 CFR Part 192, Minimum Federal Safety Standards for Gas Pipelines, shall apply.
When a structure or pipeline is employed as a ground return circuit, it shall be determined that the required electrical contact exists at all joints. The generation of an arc, sparks, or heat at any point shall cause rejection of the structures as a ground circuit.
When a structure or pipeline is continuously employed as a ground return circuit, all joints shall be bonded, and periodic inspections shall be conducted to ensure that no condition of electrolysis or fire hazard exists by virtue of such use.
The frames of all arc welding and cutting machines shall be grounded either through a third wire in the cable containing the circuit conductor or through a separate wire which is grounded at the source of the current. Grounding circuits, other than by means of the structure, shall be checked to ensure that the circuit between the ground and the grounded power conductor has resistance low enough to permit sufficient current to flow to cause the fuse or circuit breaker to interrupt the current.
All ground connections shall be inspected to ensure that they are mechanically strong and electrically adequate for the required current.
Related Code Sections
1926.351(c) Welding and Cutting, Ground Returns and Machine Grounding
A ground return cable shall have a safe current carrying capacity equal to or exceeding the specified maximum output capacity of the arc welding ...
OSHA 1926 Construction > J Welding and Cutting > 1926.351 Arc Welding and Cutting > 1926.351(c) Ground Returns and Machine Grounding
1926.351(c)(6) Welding and Cutting,
All ground connections shall be inspected to ensure that they are mechanically strong and electrically adequate for the required current ...
OSHA 1926 Construction > J Welding and Cutting > 1926.351 Arc Welding and Cutting > 1926.351(c) Ground Returns and Machine Grounding > 1926.351(c)(6)
1926.963(d)(3) Electric Power Transmission and Distribution, Isolated Ground Return
In highpower testing, the employer shall provide an isolated ground-return conductor system designed to prevent the intentional passage of current ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.963 Testing and Test Facilities > 1926.963(d) Grounding Practices > 1926.963(d)(3) Isolated Ground Return
1926.351 Welding and Cutting, Arc Welding and Cutting
A ground return cable shall have a safe current carrying capacity equal ...
1926.963(d) Electric Power Transmission and Distribution, Grounding Practices
In highpower testing, the employer shall provide an isolated ground-return conductor system designed to prevent ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.963 Testing and Test Facilities > 1926.963(d) Grounding Practices