Ground connections to the chassis or frame shall be made in an accessible location and shall be mechanically secure. Ground connections shall be by means of copper conductors and copper or copper-alloy terminals of the solderless type identified for the size of wire used. The surface on which ground terminals make contact shall be cleaned and be free from oxide or paint or shall be electrically connected through the use of a cadmium, tin, or zinc-plated internal/external-toothed lockwasher or locking terminals. Ground terminal attaching screws, rivets or bolts, nuts, and lockwashers shall be cadmium, tin, or zinc-plated except rivets shall be permitted to be unanodized aluminum where attaching to aluminum structures.
The chassis-grounding terminal of the battery shall be connected to the unit chassis with a minimum 8 AWG copper conductor. In the event the unbonded lead from the battery exceeds 8 AWG, the bonding conductor size shall be not less than that of the unbonded lead.

Related Code Sections

(4) Special Occupancies, Ground Connections
Ground connections to the chassis or frame shall be made in an accessible location and shall be mechanically secure. Ground connections shall ...
(4) Special Occupancies, Ground Connections
Ground connections to the chassis or frame shall be made in an accessible location and shall be mechanically secure. Ground connections shall ...
(1) Wiring and Protection, Additional Grounding Connection
The grounded conductor of the secondary has a grounding connection elsewhere to a continuous metal underground water piping system. In urban water ...
(A) Wiring and Protection, System Grounding Connections
A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor ...