509.1 Grease Removal Devices
Listed grease filters or other listed grease removal devices intended for use with commercial cooking operations shall be provided. Listed grease filters and grease removal devices that are removable, but not an integral component of a specific listed exhaust hood, shall be listed in accordance with UL 1046. [NFPA 96:6.1.1, 6.1.2]
509.1.1 Grease Filters, Mesh-Type
Mesh filters shall not be used unless evaluated as an integral part of a listed exhaust hood or listed in conjunction with a primary filter in accordance with UL 1046. [NFPA 96:6.1.3]
509.2 Installation
The distance between the grease removal device and the cooking surface shall be not less than 18 inches (457 mm). [NFPA 96:6.2.1.1]
509.2.1 Vertical Distance
Where grease removal devices are used in conjunction with charcoal or charcoal-type broilers, including gas or electrically heated charbroilers, a vertical distance of not less than 4 feet (1219 mm) shall be maintained between the lower edge of the grease removal device and the cooking surface. [NFPA 96:6.2.1.2]
Exceptions:
  1. For cooking equipment without exposed flame and where flue gases bypass grease removal devices, the minimum vertical distance shall be permitted to be reduced to not less than 6 inches (152 mm). [NFPA 96:6.2.1.3]
  2. Where a grease removal device is listed for separation distances less than those required in Section 509.2 and Section 509.2.1, the listing requirements shall be permitted. [NFPA 96:6.2.1.4]
  3. Grease removal devices supplied as part of listed hood assemblies shall be installed in accordance with the terms of the listing and the manufacturer's installation instructions. [NFPA 96:6.2.1.5]
509.2.2 Grease Removal Device Protection
Where the distance between the grease removal device and the appliance flue outlet (heat source) is less than 18 inches (457 mm), grease removal devices shall be protected from combustion gas outlets and from direct flame impingement occurring during normal operation of cooking appliances producing high flue gas temperatures. [NFPA 96:6.2.2.1]
509.2.2.1 Installation
This protection shall be permitted to be accomplished by the installation of a steel or stainless steel baffle plate between the heat source and the grease removal device. [NFPA 96:6.2.2.2]
509.2.2.2 Size and Location
The baffle plate shall be sized and located so that flames or combustion gases shall travel a distance not less than 18 inches (457 mm) from the heat source to the grease removal device. [NFPA 96:6.2.2.3]
509.2.2.3 Clearance
The baffle shall be located not less than 6 inches (152 mm) from the grease removal devices. [NFPA 96:6.2.2.4]
509.2.3 Grease Filters
Grease filters shall be listed and constructed of steel or other non-combustible material, and shall be of rigid construction that will not distort or crush under normal operation, handling, cleaning, or replacement.
509.2.3.1 Arrangement
Grease filters shall be arranged so that exhaust air passes through the grease filters. [NFPA 96:6.2.3.4]
509.2.3.2 Accessibility
Grease filters shall be easily accessible for removal. [NFPA 96:6.2.3.5]
509.2.3.3 Angled Installation
Grease filters shall be installed at an angle not less than 45 degrees (0.79 rad) from the horizontal. [NFPA 96:6.2.3.6]
509.2.4 Grease Drip Trays
Grease filters shall be equipped with a grease drip tray beneath their lower edges. [NFPA 96:6.2.4.1]
509.2.4.1 Size and Pitch
Grease drip trays shall be kept to the minimum size needed to collect grease and shall be pitched to drain into an enclosed metal container having a capacity not exceeding 1 gallon (4 L). [NFPA 96:6.2.4.2, 6.2.4.3]
509.2.5 Grease Filter Orientation
Grease filters that require a specific orientation to drain grease shall be clearly so designated, or the hood shall be constructed so that filters cannot be installed in the wrong orientation. [NFPA 96:6.2.5]
509.3 Solid-Fuel Grease Removal Devices
Where solid-fuel cooking equipment is provided with grease removal devices, these devices shall be in accordance with Section 517.0.

Related Code Sections

509.0 Exhaust Systems, Grease Removal Devices in Hoods
filters and grease removal devices that are removable, but not an integral component of a specific listed exhaust hood, shall be listed in accordance ...
509.2.2 Exhaust Systems, Grease Removal Device Protection
Where the distance between the grease removal device and the appliance flue outlet (heat source) is less than 18 inches (457 mm), grease removal ...
509.2.5 Exhaust Systems, Grease Filter Orientation
Grease filters that require a specific orientation to drain grease shall be clearly so designated, or the hood shall be constructed so that filters ...