506.3.12 Grease Duct Fire-Resistive Access Opening
JUMP TO FULL CODE CHAPTER
Where cleanout openings are located in ducts within a fireresistance-rated enclosure, access openings shall be provided in the enclosure at each cleanout point. Access openings shall be equipped with tight-fitting sliding or hinged doors that are equal in fire-resistive protection to that of the shaft or enclosure. An approved sign shall be placed on access opening panels with wording as follows: "ACCESS PANEL. DO NOT OBSTRUCT."
Related Code Sections
506.3.12 Exhaust Systems, Grease Duct Fire-Resistive Access Opening
Where cleanout openings are located in ducts within a fire-resistance-rated enclosure, access openings shall be provided in the enclosure at each ...
2020 FBC - Mechanical, 7th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Grease Duct Fire-Resistive Access Opening
506.3.12 Exhaust Systems, Grease Duct Fire-Resistive Access Opening
cleanout point. Access openings shall be equipped with tight-fitting sliding or hinged doors that are equal in fire-resistive protection ...
2017 FBC - Mechanical, 6th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Grease Duct Fire-Resistive Access Opening
506.3.12 Exhaust Systems, Grease Duct Fire-Resistive Access Opening
cleanout point. Access openings shall be equipped with tight-fitting sliding or hinged doors that are equal in fire-resistive protection ...
2014 FBC - Mechanical, 5th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.12 Grease Duct Fire-Resistive Access Opening
Section 506 Exhaust Systems, Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment
assemblies required to be fire-resistance rated. The grease duct system does not serve solid-fuel-fired appliances ...
2014 FBC - Mechanical, 5th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment
506.3.11 Exhaust Systems, Grease Duct Enclosures
be either field-applied or factory-built. Duct enclosures shall have a fire-resistance rating of not less than that of the assembly penetrated ...
2014 FBC - Mechanical, 5th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.11 Grease Duct Enclosures