// CODE SNIPPET
1910.106(d)(5)(v) General Purpose Public Warehouses
JUMP TO FULL CODE CHAPTER
Storage shall be in accordance with Table H-14 or H-15 and in buildings or in portions of such buildings cut off by standard firewalls. Material creating no fire exposure hazard to the flammable liquids may be stored in the same area.
NOTE 1: When 2 or more categories of materials are stored in a single
pile, the maximum gallonage permitted in that pile shall be the
smallest of the 2 or more separate maximum gallonages.
NOTE 2: Aisles shall be provided so that no container is more than 12 ft. from an aisle. Main aisles shall be at least 3 ft. wide and side aisles at least 4 ft. wide.
NOTE 3: Each pile shall be separated from each other by at least 4 ft.
NOTE 4: FP means Flashpoint.
(Number in parenthesis indicate corresponding number of 55-gal. drums.)
NOTE 1: When 1 or more categories of materials are stored in a single
pile, the maximum gallonage permitted in that pile shall be the
smallest of the 2 or more separate maximum gallonages.
NOTE 2: Aisles shall be provided so that no portable tank is more than 12 ft. from an aisle. Main aisles shall be at least 8 ft. wide and side aisles at least 4 ft. wide.
NOTE 3: Each pile shall be separated from each other by at least 4 ft.
NOTE 4: FP means Flashpoint.
Category liquid | Storage level | Gallons | |
Protected storage maximum per pile |
Unprotected storage maximum per pile |
||
1 | Ground and upper floors | 2,750 | 660 |
(50) | (12) | ||
Basement | Not permitted | Not permitted | |
2 | Ground and upper floors | 5,500 | 1,375 |
(100) | (25) | ||
Basement | Not permitted | Not permitted | |
3 | Ground and upper floors | 16,500 | 4,125 |
FP<100F | (300) | (75) | |
Basement | Not permitted | Not permitted | |
3 | Ground and upper floors | 16,500 | 4,125 |
FP≥100F | (300) | (75) | |
Basement | 5,500 (100) |
Not permitted | |
4 | Ground and upper floors | 55,000 | 13,750 |
(1,000) | (250) | ||
Basement | 8,250 (450) |
Not permitted |
NOTE 2: Aisles shall be provided so that no container is more than 12 ft. from an aisle. Main aisles shall be at least 3 ft. wide and side aisles at least 4 ft. wide.
NOTE 3: Each pile shall be separated from each other by at least 4 ft.
NOTE 4: FP means Flashpoint.
(Number in parenthesis indicate corresponding number of 55-gal. drums.)
Category | Storage level | Gallons | |
Protected storage maximum per pile |
Unprotected storage maximum per pile |
||
1 | Ground and upper floors | Not permitted | Not permitted |
Basement | Not permitted | Not permitted | |
2 | Ground and upper floors | 20,000 | 20,00 |
Basement | Not permitted | Not permitted | |
3 | Ground and upper floors | 40,000 | 5,500 |
FP<100F | Basement | Not permitted | Not permitted |
3 | Ground and upper floors | 40,000 | 5,500 |
FP≥100F | Basement | 20,000 | Not permitted |
4 | Ground and upper floors | 60,000 | 22,000 |
Basement | 20,000 | Not permitted |
NOTE 2: Aisles shall be provided so that no portable tank is more than 12 ft. from an aisle. Main aisles shall be at least 8 ft. wide and side aisles at least 4 ft. wide.
NOTE 3: Each pile shall be separated from each other by at least 4 ft.
NOTE 4: FP means Flashpoint.
Related Code Sections
1910.106(d)(5)(v) Hazardous Materials, General Purpose Public Warehouses
Storage shall be in accordance with Table H-14 or H-15 and in buildings or in portions of such buildings cut off by standard firewalls. Material ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(d) Container and Portable Tank Storage > 1910.106(d)(5) Storage Inside Building > 1910.106(d)(5)(v) General Purpose Public Warehouses
1910.331(c)(1) Electrical, Generation, Transmission, and Distribution Installations
of utilization equipment used for purposes other than generating, transmitting, or distributing electric energy (such as installations which ...
OSHA 1910 General Industry > S Electrical > 1910.331 Scope > 1910.331(c) Excluded Work by Qualified Persons > 1910.331(c)(1) Generation, Transmission, and Distribution Installations
1910.269(m)(2)(v) Special Industries,
The employer shall render any disconnecting means that are accessible to individuals outside the employer's control (for example, the general public ...
OSHA 1910 General Industry > R Special Industries > 1910.269 Electric Power Generation, Transmission, and Distribution > 1910.269(m) Deenergizing Lines and Equipment for Employee Protection > 1910.269(m)(2) General > 1910.269(m)(2)(v)
1910.1 General, Purpose and Scope
or health for specifically designated employees." The legislative purpose of this provision is to establish, as rapidly as possible and without regard ...
1910.302(a)(2)(v) Electrical,
Installations under the exclusive control of electric utilities for the purpose of communication or metering; or for the generation, control ...
OSHA 1910 General Industry > S Electrical > 1910.302 Electric Utilization Systems > 1910.302(a) Scope > 1910.302(a)(2) Not Covered > 1910.302(a)(2)(v)