6003.2.3 General Outdoor Requirements
JUMP TO FULL CODE CHAPTER
The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with Sections 6003.2.3.1 and 6003.2.3.2.
Outdoor storage or use of highly toxic or toxic solids and liquids shall not be located within 20 feet (6096 mm) of lot lines, public streets, public alleys, public ways, exit discharges or exterior wall openings. A 2-hour fire barrier without openings or penetrations extending not less than 30 inches (762 mm) above and to the sides of the storage is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
Exhaust scrubbers or other systems for processing vapors of highly toxic liquid shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure (NTP). Treatment systems and other processing systems shall be installed in accordance with the International Mechanical Code.
Related Code Sections
6003.2.3 Highly Toxic and Toxic Materials, General Outdoor Requirements
The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with Sections ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6003 Highly Toxic and Toxic Solids and Liquids > 6003.2 Outdoor Storage and Use > 6003.2.3 General Outdoor Requirements
6003.2.3 Highly Toxic and Toxic Materials, General Outdoor Requirements
The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with Sections ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6003 Highly Toxic and Toxic Solids and Liquids > 6003.2 Outdoor Storage and Use > 6003.2.3 General Outdoor Requirements
6004.3.2 Highly Toxic and Toxic Materials, General Outdoor Requirements
The general requirements applicable to the outdoor storage and use of highly toxic and toxic compressed gases shall be in accordance with Sections ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.2 General Outdoor Requirements
6004.3.2 Highly Toxic and Toxic Materials, General Outdoor Requirements
The general requirements applicable to the outdoor storage and use of highly toxic and toxic compressed gases shall be in accordance with Sections ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.2 General Outdoor Requirements
6004.3.2.3 Highly Toxic and Toxic Materials, Local Exhaust for Portable Tanks
Local exhaust for outdoor portable tanks shall be provided in accordance with the requirements set forth in Section 6004.2.2.4 ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.2 General Outdoor Requirements > 6004.3.2.3 Local Exhaust for Portable Tanks