§27-440 Gasoline and Diesel Oil Motor Vehicle Fuel Storage
JUMP TO FULL CODE CHAPTER
All volatile flammable liquids and diesel oil motor vehicle fuel storage tanks shall be installed below ground and vented to the open air except for such aboveground installation as may be authorized by the rules of the fire commissioner. The installation and venting of storage tanks shall be in accordance with applications and plans approved by the commissioner and shall also meet the requirements of chapter four of this title and the rules of the fire commissioner. Except as otherwise provided for in chapter four of this title or the rules of the fire commissioner, underground tank installations shall comply with the following:
(a) The tops of the tanks shall be at least two feet below finished grade and at least two feet below the level of any cellar or basement floor within ten feet of the tanks.
(b) Tanks shall be supported on foundations complying with subchapter eleven of this chapter.
(c) Tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance from any part of a tank to the nearest wall of any basement, pit or cellar, or from any property line that may be built upon, shall not be less than three feet.
(d) Tanks shall be covered with a structurally supported reinforced concrete slab at least eight inches thick extending at least twelve inches beyond the horizontal outlines of the tanks and placed over a coverage of suitable clean backfill material.
(e) All concrete shall have a minimum compressive strength of twenty-five hundred pounds per square inch at twenty-eight days.
(a) The tops of the tanks shall be at least two feet below finished grade and at least two feet below the level of any cellar or basement floor within ten feet of the tanks.
(b) Tanks shall be supported on foundations complying with subchapter eleven of this chapter.
(c) Tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance from any part of a tank to the nearest wall of any basement, pit or cellar, or from any property line that may be built upon, shall not be less than three feet.
(d) Tanks shall be covered with a structurally supported reinforced concrete slab at least eight inches thick extending at least twelve inches beyond the horizontal outlines of the tanks and placed over a coverage of suitable clean backfill material.
(e) All concrete shall have a minimum compressive strength of twenty-five hundred pounds per square inch at twenty-eight days.
Related Code Sections
§27-440 Special Uses and Occupancies, Gasoline and Diesel Oil Motor Vehicle Fuel Storage
All volatile flammable liquids and diesel oil motor vehicle fuel storage tanks shall be installed below ground and vented to the open air except ...
NYC 1968 Code (Vol I) > 7 Special Uses and Occupancies > 8 Automotive Service Stations > §27-440 Gasoline and Diesel Oil Motor Vehicle Fuel Storage
§27-451 Special Uses and Occupancies, Classification
having fuel storage tanks in excess of twenty-six gallon capacity; or used for the parking of vehicles of any size, and in which mechanical repair, body ...
§27-827 Heating and Combustion Equipment, General Requirements
commercial grades: range oil or no. 1 fuel oil; diesel oil or no. 2 fuel oil; no. 4 fuel oil; no. 5 fuel oil; no. 6 fuel oil. Except as provided ...
NYC 1968 Code (Vol I) > 14 Heating and Combustion Equipment > 17 Fuel Oil Equipment > §27-827 General Requirements
406.5 Special Detailed Requirements Based on Use and Occupancy, Motor Fuel-Dispensing Facilities
in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided the panels are located at least 10 feet (3048 mm) from any ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 406 Motor Vehicle-Related Occupancies > 406.5 Motor Fuel-Dispensing Facilities
406.5 Special Detailed Requirements Based on Use and Occupancy, Motor Fuel-Dispensing Facilities
to be installed in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided the panels are located at least 10 feet (3048 mm) from any ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 406 Motor-Vehicle-Related Occupancies > 406.5 Motor Fuel-Dispensing Facilities