42.7.2.6.2.8 Gaseous Fuel Dispensing Areas
Go To Full Code Chapter
At least one portable fire extinguisher shall be provided for each gaseous fuel
dispenser or group of dispensers so as not to exceed a maximum travel distance of 50 ft (15 m) but not less than 15 ft (4.6
m) to any single portable fire extinguisher. [30A:9.2.5.2.8]