Gas sampling shall be performed continuously. Sample analysis shall be processed immediately after sampling, except as follows:
- For HPM gases, sample analysis shall be performed at intervals not exceeding 30 minutes.
- For toxic gases that are not HPM, sample analysis shall be performed at intervals not exceeding 5 minutes, in accordance with Section 6004.2.2.7.
- Where a less frequent or delayed sampling interval is approved.
Related Code Sections
916.7 Fire Protection and Life Safety Systems, Gas Sampling
Gas sampling shall be performed continuously. Sample analysis shall be processed immediately after sampling, except as follows: For HPM gases ...
2020 Fire Code of NYS > 9 Fire Protection and Life Safety Systems > 916 Gas Detection Systems > 916.7 Gas Sampling
3704.2.2.10.3 Highly Toxic and Toxic Materials, Valve Closure
Automatic closure of shutoff valves shall be in accordance with the following: When the gas-detection sampling point initiating the gas detection ...
2010 Fire Code of NY > 37 Highly Toxic and Toxic Materials > 3704 Highly Toxic and Toxic Compressed Gases > 3704.2 Indoor Storage and Use > 3704.2.2 General Indoor Requirements > 3704.2.2.10 Gas Detection System > 3704.2.2.10.3 Valve Closure
6004.2.2.10.3 Highly Toxic and Toxic Materials, Valve Closure
Automatic closure of shutoff valves shall be in accordance with the following: Where the gas-detection sampling point initiating the gas detection ...
2020 Fire Code of NYS > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.2 Indoor Storage and Use > 6004.2.2 General Indoor Requirements > 6004.2.2.10 Gas Detection System > 6004.2.2.10.3 Valve Closure
6004.2.2.10.4 Highly Toxic and Toxic Materials, Valve Closure
Automatic closure of shutoff valves shall be in accordance with the following: Where the gas-detection sampling point initiating the gas detection ...
Fire Code 2015 of New York State > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.2 Indoor Storage and Use > 6004.2.2 General Indoor Requirements > 6004.2.2.10 Gas Detection System > 6004.2.2.10.4 Valve Closure
908.3.3 Fire Protection Systems, Valve Closure
The automatic closure of shutoff valves shall be in accordance with the following:
When the gas-detection sampling point initiating the gas ...
Building Code 2015 of New York State > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.3 Highly Toxic and Toxic Materials > 908.3.3 Valve Closure