Gas meter piping supplying gas to a building at a pressure in excess of 1/2 psig (3.4 kPa gauge) shall be provided with a regulator that will reduce the pressure of the gas to 1/2 psig (3.4 kPa gauge) or less prior to entering the gas distribution piping in the building, except where the use of higher pressure is permitted. Where gas distribution pressure in excess of 1/2 psig (3.4 kPa gauge) is permitted, it shall be regulated to not exceed the maximum pressure level as permitted by the code or the commissioner.
Inside gas meter piping operating at a pressure in excess of 15 psig (103.4 kPa gauge) shall comply with the following:
- Where such piping is greater than 4 inches (101.6 mm) in diameter, the meter piping shall be installed in a properly ventilated meter room of 3-hour fire-rated construction.
- The maximum total developed length from the outlet of the service head valve to the inlet of the farthest regulator shall be limited as follows:
SERVICE LINE VALVE SIZE MAXIMUM DISTANCE
(LINEAR FEET OF PIPE)Up to 2-inch (51 mm) pipe size4 feet (1219 mm) Over 2-inch (51 mm) through 4-inch
(102 mm) pipe size8 feet (2438 mm) Over 4-inch (102 mm) through 8-inch
(203 mm) pipe size15 feet (4572 mm) 10-inch (254 mm) pipe size and larger20 feet (6096 mm) - Where these maximum distances cannot be met, the following shall be required:
FOOTAGE (LINEAR FEET OF PIPE) IN EXCESS OF ABOVE REQUIREMENTS ADDITIONAL REQUIREMENTS Up to 5 feet (1534 mm) The meter room shall have 3-hour fire-rated construction and adequate ventilation. Over 5 feet (1524 mm) through 10 feet (3048 mm) Above requirements plus a combustible gas-detection alarm system Over 10 feet (3048 mm) through 15 feet (4572 mm) Above requirements plus special inspection by the customer, or his or her representative as required by the New York City Building Code. Over 15 feet (4572 mm) through 20 feet (6096 mm) Above requirements plus (i) automatic gas shutoff devices; and (ii) explosion venting per
NFPA 68 and NFPA 69 or alternative ventilation acceptable to the commissionerOver 20 feet (6096 mm) Above requirements plus suitable fire protection approved by the commissioner
When located inside the building, each regulator shall be provided with a vent pipe that leads directly to the outdoor air. The vent pipe shall be sized according to local utility requirements. The vent outlet shall not be located under a window or any opening leading back into the premises or located below any overhang or projection. No gas regulator vent outlet shall be covered over, plugged up, or otherwise obstructed, and all gas vents shall be identified by suitable marking on the outlet on the outside of the building. For buildings located in flood hazard areas, gas regulator vent outlets shall be installed in accordance with the additional requirements of Appendix G of the New York City Building Code.
Related Code Sections
E.2 Meters and Gas Service Piping, Gas Regulator and Gas Regulator Vent Outlets
not be located under a window or any opening leading back into the premises or located below any overhang or projection. No gas regulator vent outlet shall ...
NYC Fuel Gas Code 2014 > E Meters and Gas Service Piping > E.2 Gas Regulator and Gas Regulator Vent Outlets
E.2 Meters and Gas Service Piping, Gas Regulator and Gas Regulator Vent Outlets
any overhang or projection. No gas regulator vent outlet shall be covered over, plugged up, or otherwise obstructed, and all gas vents shall ...
NYC Fuel Gas Code 2022 > E Meters and Gas Service Piping > E.2 Gas Regulator and Gas Regulator Vent Outlets
Reference Standard 16 Plumbing and Gas Piping [PDF] (page 5)
Requirements for Gas Piping Gas Service Piping Connections Gas Regulator and Gas Regulator Vent Outlets Outside Gas Cut-Off Gas Meter Location Gas ...
Article 15 Plumbing and Gas Piping [PDF] (page 31)
(14.13.2.1). §C26-1324.1 Gas Regulator and Gas Regulator Vent Outlets.-Each and every existing or hereafter installed gas service connection ...
Reference Standard 16 Plumbing and Gas Piping [PDF] (page 67)
**Local Law 30-1982 **P115.4-Gas Regulator And Gas Regulator Vent Outlets.-Gas meter piping supplying gas to a building at a pressure in excess of 1/2 ...