1210.3.3 Gas Piping to Be Sloped
Go To Full Code Chapter
Piping for other than dry gas conditions shall be sloped not less than 1/4 inch in 15 feet (6.4 mm in 4.6 m) to prevent traps. [NFPA 54:7.2.4]
1210.3.3.1 Ceiling Locations
Gas piping shall be permitted to be installed in accessible spaces between a fixed ceiling and a dropped ceiling, whether or not such spaces are used as a plenum. Valves shall not be located in such spaces.
Exception: Appliance or equipment shutoff valves required by this code shall be permitted to be installed in accessible spaces containing vented appliances.