516.2.1 Gas/Electrically Fueled Cooking Appliances
JUMP TO FULL CODE CHAPTER
Gas-fueled or electrically fueled cooking appliances
shall be used. Listed gas-fueled equipment
designed for use with specific recirculating systems shall
have the flue outlets connected in the intended manner.
Gas-fueled appliances shall have not less than 18 inches
(457 mm) of clearance from the flue outlet to the filter
inlet in accordance with Section 509.2.2 through Section
509.2.2.3 and shall be in accordance with the installation
requirements of NFPA 54 or NFPA 58. [NFPA 96:13.2.1
- 13.2.3]
Related Code Sections
516.2.1 Exhaust Systems, Gas/Electrically Fueled Cooking Appliances
Gas-fueled or electrically fueled cooking appliances shall
be used. Listed gas-fueled equipment designed for use
with specific recirculating systems ...
California Mechanical Code 2016 > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.1 Gas/Electrically Fueled Cooking Appliances
516.2.1 Exhaust Systems, Gas/Electrically Fueled Cooking Appliances
Gas-fueled or electrically fueled cooking appliances
shall be used. Listed gas-fueled equipment
designed for use with specific recirculating systems ...
California Mechanical Code 2019 > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.1 Gas/Electrically Fueled Cooking Appliances
517.7.7 Exhaust Systems, Auxiliary Fuel
with auxiliary electric, gas, oil, or other fuel for ignition or supplemental heat and the appliance is also served by a portion of a fire-extinguishing ...
California Mechanical Code 2016 > 5 Exhaust Systems > 517.0 Solid-Fuel Cooking Operations > 517.7 Fire-Extinguishing Equipment for Solid-Fuel Cooking > 517.7.7 Auxiliary Fuel
517.7.7 Exhaust Systems, Auxiliary Fuel
with auxiliary
electric, gas, oil, or other fuel for ignition or supplemental
heat and the appliance is also served by a portion
of a fire-extinguishing ...
California Mechanical Code 2019 > 5 Exhaust Systems > 517.0 Solid-Fuel Cooking Operations > 517.7 Fire-Extinguishing Equipment for Solid-Fuel Cooking > 517.7.7 Auxiliary Fuel
513.4 Exhaust Systems, Fuel and Electric Power Shutoff
Upon activation
of a fire-extinguishing system for a cooking operation,
sources of fuel and electric power that produce heat to equipment
requiring ...
California Mechanical Code 2019 > 5 Exhaust Systems > 513.0 Fire-Extinguishing Equipment > 513.4 Fuel and Electric Power Shutoff