1926.306(b)(3) Gages and Valves
JUMP TO FULL CODE CHAPTER
Every air receiver shall be equipped with an indicating pressure gage (so located as to be readily visible) and with one or more spring-loaded safety valves. The total relieving capacity of such safety valves shall be such as to prevent pressure in the receiver from exceeding the maximum allowable working pressure of the receiver by more than 10 percent.
Safety appliances, such as safety valves, indicating devices and controlling devices, shall be constructed, located, and installed so that they cannot be readily rendered inoperative by any means, including the elements.
All safety valves shall be tested frequently and at regular intervals to determine whether they are in good operating condition.
[58 FR 35176, June 30, 1993]
[58 FR 35176, June 30, 1993]
No valve of any type shall be placed between the air receiver and its safety valve or valves.
Related Code Sections
1926.306(b)(3) Tools - Hand and Power, Gages and Valves
Every air receiver shall be equipped with an indicating pressure gage (so located as to be readily visible) and with one or more spring-loaded safety ...
OSHA 1926 Construction > I Tools - Hand and Power > 1926.306 Air Receivers > 1926.306(b) Installation and Equipment Requirements > 1926.306(b)(3) Gages and Valves
1926.152(i)(3)(v)(B) Fire Protection and Prevention,
Openings for manual gaging, if independent of the fill pipe, shall be provided with a liquid-tight cap or cover. If inside a building, each ...
OSHA 1926 Construction > F Fire Protection and Prevention > 1926.152 Flammable Liquids > 1926.152(i) Tank Storage > 1926.152(i)(3) Installation of Underground Tanks > 1926.152(i)(3)(v) Tank Openings Other Than Vents > 1926.152(i)(3)(v)(B)
1926.152(i)(4)(iv)(D) Fire Protection and Prevention,
Openings for manual gaging, if independent of the fill pipe (see paragraph (i)(4)(iv)(F) of this section), shall be provided with a vaportight cap ...
OSHA 1926 Construction > F Fire Protection and Prevention > 1926.152 Flammable Liquids > 1926.152(i) Tank Storage > 1926.152(i)(4) Installation of Tanks Inside of Buildings > 1926.152(i)(4)(iv) Tank Openings Other Than Vents > 1926.152(i)(4)(iv)(D)
1926.306 Tools - Hand and Power, Air Receivers
shall be equipped with an indicating pressure gage (so located as to be readily visible) and with one or more spring-loaded safety valves. The total ...
1926.152(i)(4)(iv) Fire Protection and Prevention, Tank Openings Other Than Vents
normally flow shall be provided with an internal or external valve located as close as practical to the shell of the tank. Such valves, when external ...
OSHA 1926 Construction > F Fire Protection and Prevention > 1926.152 Flammable Liquids > 1926.152(i) Tank Storage > 1926.152(i)(4) Installation of Tanks Inside of Buildings > 1926.152(i)(4)(iv) Tank Openings Other Than Vents