1905.2.1 Fuel Tanks Connected to Engine-Driven Building Services Equipment
JUMP TO FULL CODE CHAPTER
Fuel tanks piped to and supplying fuel
for engine-driven building service equipment may be
engine-mounted, located inside of a building, outside of a
building, or on a roof in accordance with NFPA 37 or NFPA 30.
Engine-mounted tanks located outdoors may be located in accordance
with Section 4.1.4 of NFPA 37 and shall be vented in
accordance with NFPA 30. Engine-mounted tanks shall
be provided with adequate clearance to enable filling,
maintenance, and testing, shall be safeguarded against
public access, and shall be protected from impact.
Fuel tanks, other than engine-mounted tanks, piped to and supplying the engine shall be located, installed, and vented in accordance with the applicable sections of NFPA 37 or located, installed, and vented in accordance with NFPA 30.
Related Code Sections
1905.2.1 Special Fuel-Burning Equipment, Fuel Tanks Connected to Engine-Driven Building Services Equipment
Fuel tanks piped to and supplying fuel
for engine-driven building service equipment may be
engine-mounted, located inside of a building, outside ...
Ohio Residential Code 2013 > 19 Special Fuel-Burning Equipment > 1905 Engine and Gas-Turbine Powered Equipment and Appliances > 1905.2 Engine-Driven Equipment and Appliances > 1905.2.1 Fuel Tanks Connected to Engine-Driven Building Services Equipment
915.2.1 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Fuel Tanks Connected to Engine-Driven Building Service Equipment
Fuel tanks piped to and supplying fuel for engine-driven building service equipment may be engine mounted, located inside of a building, outside ...
Ohio Mechanical Code 2011 > 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment > 915 Engine and Gas Turbine-Poweredequipment and Appliances > 915.2 Engine-Driven Equipment and Appliances > 915.2.1 Fuel Tanks Connected to Engine-Driven Building Service Equipment
1905.2 Special Fuel-Burning Equipment, Engine-Driven Equipment and Appliances
Fuel tanks piped to and supplying fuel
for engine-driven building service equipment may be
engine-mounted, located inside of a building, outside ...
Ohio Residential Code 2013 > 19 Special Fuel-Burning Equipment > 1905 Engine and Gas-Turbine Powered Equipment and Appliances > 1905.2 Engine-Driven Equipment and Appliances
2702.1.1.1 Electrical, Engine-Driven Generators
to and supplying fuel for engine-driven generator assemblies may be engine-mounted, located inside of a building, outside of a building, or on a roof ...
Ohio Building Code 2011 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.1 Installation > 2702.1.1 Stationary Generators > 2702.1.1.1 Engine-Driven Generators
Section 3402.1.1.1 General Requirements, Engine-Driven Generators
to and supplying fuel for
engine-driven generator assemblies may be
engine-mounted, located inside of a building, outside
of a building, or on a roof ...
Ohio Residential Code 2013 > 34 General Requirements > 3402 Emergency and Standby Power Systems > 3402.1 Installation > 3402.1.1 Stationary Generators > 3402.1.1.1 Engine-Driven Generators