603.1.4 Fuel Oil
JUMP TO FULL CODE CHAPTER
The grade of fuel oil used in a burner shall be that for which the burner is approved and as stipulated by the burner manufacturer. Oil containing gasoline shall not be used. Waste crankcase oil shall be an acceptable fuel in Group F, M and S occupancies where utilized in equipment listed for use with waste oil and where such equipment is installed in accordance with the manufacturer's instructions and the terms of its listing.
Related Code Sections
603.1.4 Building Services and Systems, Fuel Oil
The grade of fuel oil used in a burner shall be that for which the burner is approved and as stipulated by the burner manufacturer. Oil containing ...
Fire Code 2018 of Colorado > 6 Building Services and Systems > 603 Fuel-Fired Appliances > 603.1 Installation > 603.1.4 Fuel Oil
605.1.3 Building Services and Systems, Fuel Oil
The grade of fuel oil used in an oil burner shall be that for which the oil burner is approved and as stipulated by the oil burner ...
Fire Code 2021 of Colorado > 6 Building Services and Systems > 605 Fuel-Fired Appliances > 605.1 General > 605.1.3 Fuel Oil
Section 1307 Fuel Oil Piping and Storage, Fuel Oil Valves
A shutoff valve shall be installed on the fuel-oil supply line at the entrance to the building. Inside or above-ground tanks are permitted to have ...
Section 1307 Fuel Oil Piping and Storage, Fuel Oil Valves
A shutoff valve shall be installed on the fuel-oil supply line at the entrance to the building. Inside or above-ground tanks are permitted to have ...
Section 1307 Fuel Oil Piping and Storage, Fuel Oil Valves
A shutoff valve shall be installed on the fuel-oil supply line at the entrance to the building. Inside or above-ground tanks are permitted to have ...