1604.3.7 Framing Supporting Glass
JUMP TO FULL CODE CHAPTER
The deflection of framing members supporting glass subjected to 0.6 times the "component and cladding" wind loads shall not exceed either of the following:
- 1/175 of the length of span of the framing member, for framing members having a length not more than 13 feet 6 inches (4115 mm).
- 1/240 of the length of span of the framing member + 1/4 inch (6.4 mm), for framing members having a length greater than 13 feet 6 inches (4115 mm).
Related Code Sections
1604.3.7 Structural Design, Framing Supporting Glass
The deflection of framing members supporting glass subjected to 0.6 times the "component and cladding" wind loads shall not exceed either ...
Building Code 2018 of Wyoming > 16 Structural Design > 1604 General Design Requirements > 1604.3 Serviceability > 1604.3.7 Framing Supporting Glass
2405.4 Glass and Glazing, Framing
are permitted to be used for sash and frames. Framing supporting sloped glazing and skylights shall be designed to resist the tributary roof loads in Chapter 16 ...
Building Code 2015 of Wyoming > 24 Glass and Glazing > 2405 Sloped Glazing and Skylights > 2405.4 Framing
2405.4 Glass and Glazing, Framing
are permitted to be used for sash and frames. Framing supporting sloped glazing and skylights shall be designed to resist the tributary roof loads in Chapter 16 ...
Building Code 2018 of Wyoming > 24 Glass and Glazing > 2405 Sloped Glazing and Skylights > 2405.4 Framing
2403.3 Glass and Glazing, Framing
To be considered firmly supported, the framing members for each individual pane of glass shall be designed so the deflection of the edge of the glass ...
Building Code 2018 of Wyoming > 24 Glass and Glazing > 2403 General Requirements for Glass > 2403.3 Framing
2403.3 Glass and Glazing, Framing
To be considered firmly supported, the framing members for each individual pane of glass shall be designed so the deflection of the edge of the glass ...
Building Code 2015 of Wyoming > 24 Glass and Glazing > 2403 General Requirements for Glass > 2403.3 Framing