Openings in roofs and ceilings shall be framed with header and trimmer joists. Header joist spans shall not exceed 4 feet (1219 mm) in length. Header and trimmer joists shall be fabricated from joist and track members having a minimum size and thickness equivalent to the adjacent ceiling joists or roof rafters and shall be installed in accordance with Figures R804.3.5(1) and R804.3.5(2). Each header joist shall be connected to trimmer joists with not less than four 2-inch by 2-inch (51 by 51 mm) clip angles. Each clip angle shall be fastened to both the header and trimmer joists with four No. 8 screws, evenly spaced, through each leg of the clip angle. The steel thickness of the clip angles shall be not less than that of the ceiling joist or roof rafter. Each track section for a built-up header or trimmer joist shall extend the full length of the joist (continuous).



For SI: 1 foot = 304.8 mm.
FIGURE R804.3.5(1)
ROOF OR CEILING OPENING




For SI: 1 inch = 25.4 mm.
FIGURE R804.3.5(2)
HEADER TO TRIMMER CONNECTION

Related Code Sections

R804.3.5 Roof-Ceiling Construction, Framing of Openings in Roofs and Ceilings
Openings in roofs and ceilings shall be framed with header and trimmer joists. Header joist spans shall not exceed 4 feet (1219 mm) in length. Header ...
R802.9 Roof-Ceiling Construction, Framing of Openings
Openings in roof and ceiling framing shall be framed with header and trimmer joists. Where the header joist span does not exceed 4 feet (1219 mm ...