Foundations that adjoin frost-protected shallow foundations shall be protected from frost in accordance with Section R403.1.4.
R403.3.1.1 Attachment to Unheated Slab-on-Ground Structure
Vertical wall insulation and horizontal insulation of frost-protected shallow foundations that adjoin a slab-on-ground foundation that does not have a monthly mean temperature maintained at not less than 64°F (18°C) shall be in accordance with Figure R403.3(3) and Table R403.3(1). Vertical wall insulation shall extend between the frost-protected shallow foundation and the adjoining slab foundation. Required horizontal insulation shall be continuous under the adjoining slab foundation and through any foundation walls adjoining the frost-protected shallow foundation. Where insulation passes through a foundation wall, it shall be either of a type complying with this section and having bearing capacity equal to or greater than the structural loads imposed by the building, or the building shall be designed and constructed using beams, lintels, cantilevers or other means of transferring building loads such that the structural loads of the building do not bear on the insulation.
R403.3.1.2 Attachment to Heated Structure
Where a frost-protected shallow foundation abuts a structure that has a monthly mean temperature maintained at not less than 64°F (18°C), horizontal insulation and vertical wall insulation shall not be required between the frost-protected shallow foundation and the adjoining structure. Where the frost-protected shallow foundation abuts the heated structure, the horizontal insulation and vertical wall insulation shall extend along the adjoining foundation in accordance with Figure R403.3(4) a distance of not less than Dimension A in Table R403.3(1).
Exception: Where the frost-protected shallow foundation abuts the heated structure to form an inside corner, vertical insulation extending along the adjoining foundation is not required.
Upcodes Diagrams

Related Code Sections

1809.5 Soils and Foundations, Frost Protection
Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost ...
1809.5 Soils and Foundations, Frost Protection
Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost ...