P2910.9.4 Foundation and Supports
Go To Full Code Chapter
Storage tanks shall be supported on a firm base capable of withstanding the weight of the storage tank when filled to capacity. Storage tanks shall be supported in accordance with this code.
P2910.9.4.1 Ballast
Where the soil can become saturated, an underground storage tank shall be ballasted or otherwise secured to prevent the tank from floating out of the ground when empty. The combined weight of the tank and hold-down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the storage tank weight when full, consistent with the bearing capability of adjacent soil.
P2910.9.4.2 Structural Support
Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage and with minimal deformation when empty or filled with water.
Related Code Sections
1301.9.3 Nonpotable Water Systems, Foundation and Supports
the installation requires a foundation, the foundation shall be flat and shall be designed to support the weight of the storage tank when full ...
16.4.1 Liquid Nitrous Oxide Systems, Foundations and Supports
be provided with noncombustible concrete or masonry foundations or structural steel supports on firm concrete or masonry foundations ...
5503.1.3 Cryogenic Fluids, Foundations and Supports
Containers shall be provided with substantial concrete or masonry foundations, or structural steel supports on firm concrete or masonry foundations ...
5503.1.3 Cryogenic Fluids, Foundations and Supports
Containers shall be provided with substantial concrete or masonry foundations, or structural steel supports on firm concrete or masonry foundations ...
8.2.3 Cryogenic Fluids, Foundations and Supports
Stationary tanks shall be provided with concrete or masonry foundations or structural steel supports on firm concrete or masonry foundations ...