419.1 Formula Preparation Area
JUMP TO FULL CODE CHAPTER
Air shall be supplied
over the formulation preparation area by group E, nonaspirating
supply diffusers. Air shall be returned or exhausted by
registers located not less than 3 inches (76 mm) nor more
than 8 inches (203 mm) above the finished floor in the
cleanup area.
Related Code Sections
419.1 Ventilation Air, Formula Preparation Area
Air shall be supplied
over the formulation preparation area by group E, nonaspirating
supply diffusers. Air shall be returned or exhausted ...
California Mechanical Code 2019 > 4 Ventilation Air > 419.0 Neonatal Intensive Care Units > 419.1 Formula Preparation Area
1224.29.2.10.2 Interior Environment, Formula Preparation Room
The formula preparation room shall include the following: A separate cleanup area for washing and sanitizing. This area shall include a handwashing ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.29 Intensive Care Units > 1224.29.2 Newborn Intensive Care Units (NICU) > 1224.29.2.10 Infant Formula Facilities > 1224.29.2.10.2 Formula Preparation Room
407.4.1.5 Ventilation Air,
preparation room, NICU treatment area/room
3
30%
90%
99.97% 3
(8)
(14)
(17)
Protective ...
California Mechanical Code 2019 > 4 Ventilation Air > 407.0 Ventilation System Details > 407.4 Air Circulation > 407.4.1 > 407.4.1.5
1224.30 Interior Environment, Pediatric and Adolescent Unit
Space for preparation and storage of infant formula shall ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.30 Pediatric and Adolescent Unit
1224.29.2.10.1 Interior Environment, Location
Where infant formula is prepared on site, direct access from the formula preparation room to any infant care room is prohibited. The formula ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.29 Intensive Care Units > 1224.29.2 Newborn Intensive Care Units (NICU) > 1224.29.2.10 Infant Formula Facilities > 1224.29.2.10.1 Location