1003.3.2 Food Waste Grinders
JUMP TO FULL CODE CHAPTER
Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the discharge before connecting to the grease interceptor. Solids interceptors and grease interceptors shall be sized and rated for the discharge of the food waste grinder. Emulsifiers, chemicals, enzymes and bacteria shall not discharge into the food waste grinder.
Related Code Sections
1003.3.2 Traps, Interceptors and Separators, Food Waste Grinders
Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the discharge before connecting to the grease ...
DC Plumbing Code 2013 > 10 Traps, Interceptors and Separators > 1003 Interceptors and Separators > 1003.3 Grease Interceptors > 1003.3.2 Food Waste Grinders
Section P2716 Plumbing Fixtures, Food Waste Grinder
Food waste grinders shall be connected to a drain of not less than 1 1 / 2 inches (38 mm) in diameter ...
Section 413 Fixtures, Faucets and Fixture Fittings, Food Waste Grinder Units
Domestic food waste grinders shall conform to ASSE 1008. Food waste grinders shall not increase the drainage fixture unit load on the sanitary ...
413.4 Fixtures, Faucets and Fixture Fittings, Water Supply Required
All food waste grinders shall be provided with a supply of cold water. The water supply shall be protected against backflow by an air gap ...
DC Plumbing Code 2013 > 4 Fixtures, Faucets and Fixture Fittings > 413 Food Waste Grinder Units > 413.4 Water Supply Required
802.1.6 Indirect/Special Waste, Domestic Dishwashing Machines
with Section 802.2, or discharge into a wye-branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste grinder. The ...
DC Plumbing Code 2013 > 8 Indirect/Special Waste > 802 Indirect Wastes > 802.1 Where Required > 802.1.6 Domestic Dishwashing Machines