1015.1 Purpose
The purpose of this section is to provide the necessary criteria for the sizing, application, and installation of FOG disposal systems designated as a pretreatment or discharge water quality compliance strategy.
1015.2 Components, Materials, and Equipment
FOG disposal systems, including components, materials, and equipment necessary for the proper function of the system, shall comply with ASME A112.14.6.
1015.3 Sizing and Installation
FOG disposal systems shall be sized and installed in accordance with the manufacturer's installation instructions.
1015.4 Performance
FOG disposal systems shall produce an effluent quality not to exceed 5.84 grains per gallon (gr/gal) (100 mg/L) FOG.