3108F.6.4 Foam Supply (N/E)
JUMP TO FULL CODE CHAPTER
Product flammability, foam type, water flow rates and application duration shall be considered in foam supply calculations.
Fixed foam proportioning equipment shall be located at a distance of at least 100 ft from the sumps, manifolds and loading arms, except where hydraulic limits of the foam delivery system require closer proximity.
MOTs shall have a program to ensure that foam is replaced according to the manufacturer's recommendations.