11B-411.4.11 Floor Destination Indicators
Go To Full Code Chapter
There shall be on each elevator car door jamb a visual display indicating floor destinations.
11B-411.4.11.1 Height
Floor destination characters shall be 1 inch (25 mm) high minimum complying with Section 11B-703.5.3.
11B-411.4.11.2 Contrast
Visual display shall provide contrast with light characters on a dark background or dark characters on a light background. The background shall be solid and static.
11B-411.4.11.3 Duration
Floor destination characters shall be displayed upon elevator car arrival at the input floor and shall not extinguish until the elevator car arrives at the destination floor.
Related Code Sections
11B-411.4.11 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Floor Destination Indicators
There shall be on each elevator car door jamb a visual display indicating floor destinations ...
11B-411.4.11 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Floor Destination Indicators
There shall be
on each elevator car door jamb a visual display indicating
floor destinations ...
11B-411.4.11 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Floor Destination Indicators
There shall be on each elevator car door jamb a visual display indicating floor destinations ...
11B-411.4.11.2 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Contrast
Visual display shall provide contrast with light characters on a dark background or dark characters on a light background. The background shall ...
11B-411.4.11.3 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Duration
Floor destination characters
shall be displayed upon elevator car arrival at the input
floor and shall not extinguish until the elevator car
arrives ...