M1803.3.1 Floor, Ceiling and Wall Penetrations
JUMP TO FULL CODE CHAPTER
A chimney connector or vent connector shall not pass through any floor or ceiling. A chimney connector or vent connector shall not pass through a wall or partition unless the connector is listed and labeled for wall pass-through, or is routed through a device listed and labeled for wall pass-through and is installed in accordance with the conditions of its listing and label. Connectors for oil-fired appliances listed and labeled for Type L vents, passing through walls or partitions shall be in accordance with the following:
- Type L vent material for oil appliances shall be installed with not less than listed and labeled clearances to combustible material.
- Single-wall metal pipe shall be guarded by a ventilated metal thimble not less than 4 inches (102 mm) larger in diameter than the vent connector. A minimum 6 inches (152 mm) of clearance shall be maintained between the thimble and combustibles.
Related Code Sections
M1803.3.1 Chimneys and Vents, Floor, Ceiling and Wall Penetrations
A chimney connector or vent connector shall not pass through any floor or ceiling. A chimney connector or vent connector shall not pass through ...
Residential Code 2015 of Alabama > 18 Chimneys and Vents > M1803 Chimney and Vent Connectors > M1803.3 Installation > M1803.3.1 Floor, Ceiling and Wall Penetrations
M2105.19 Hydronic Piping, Pipe Penetrations
Openings for pipe penetrations in walls, floors and ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building ...
Residential Code 2015 of Alabama > 21 Hydronic Piping > M2105 Ground-Source Heat-Pump System Loop Piping > M2105.19 Pipe Penetrations
1206.4 Hydronic Piping, Pipe Penetrations
Openings for pipe penetrations in walls, floors or ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building ...
Mechanical Code 2015 of Alabama > 12 Hydronic Piping > 1206 Piping Installation > 1206.4 Pipe Penetrations
1206.4 Hydronic Piping, Pipe Penetrations
Openings for pipe penetrations in walls, floors or ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building ...
Mechanical Code 2009 of Alabama > 12 Hydronic Piping > 1206 Piping Installation > 1206.4 Pipe Penetrations
1210.8.2 Hydronic Piping, Pipe Penetrations
Openings for pipe penetrations in walls, floors and ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building ...
Mechanical Code 2015 of Alabama > 12 Hydronic Piping > 1210 Plastic Pipe Ground-Source Heat Pump Loop Systems > 1210.8 Installation > 1210.8.2 Pipe Penetrations