9.7.4 Flexural Reinforcement in Prestressed Beams
Go To Full Code Chapter
9.7.4.1
External tendons shall be attached to the member in a manner that maintains the specified eccentricity between the tendons and the concrete centroid through the full range of anticipated member deflections.
9.7.4.2
If nonprestressed reinforcement is required to satisfy flexural strength, the detailing requirements of 9.7.3 shall be satisfied.
9.7.4.3 Termination of Prestressed Reinforcement
9.7.4.3.1
Post-tensioned anchorage zones shall be designed and detailed in accordance with 25.9.
9.7.4.3.2
Post-tensioning anchorages and couplers shall be designed and detailed in accordance with 25.8.
9.7.4.4 Termination of Deformed Reinforcement in Beams With Unbonded Tendons
9.7.4.4.1
Length of deformed reinforcement required by 9.6.2.3 shall be in accordance with (a) and (b):
(a) At least ān/3 in positive moment areas and be centered in those areas
(b) At least ān/6 on each side of the face of support in negative moment areas
Related Code Sections
9.7.4 Beams, Flexural Reinforcement in Prestressed Beams
If nonprestressed reinforcement is required to satisfy flexural strength, the detailing requirements of 9.7.3 shall be satisfied ...
9.7.4 Beams, Flexural Reinforcement in Prestressed Beams
If nonprestressed reinforcement is required to satisfy flexural strength, the detailing requirements of 9.7.3 shall be satisfied ...
9.6.2 Beams, Minimum Flexural Reinforcement in Prestressed Beams
For beams with bonded prestressed reinforcement, total quantity of As and Aps shall be adequate to develop a factored load at least 1.2 times ...
9.6.2 Beams, Minimum Flexural Reinforcement in Prestressed Beams
For beams with bonded prestressed reinforcement, total quantity of As and Aps shall be adequate to develop a factored load at least 1.2 times ...
9.7.4.2 Beams,
If nonprestressed reinforcement is required to satisfy flexural strength, the detailing requirements of 9.7.3 shall be satisfied ...