E 404.1 Flexible Gas Connector
Go To Full Code Chapter
Except for manufactured homes located on an all-weather wood, concrete, or concrete block foundation system or on a foundation constructed in accordance with the local building code or, in the absence of a local code, with a recognized model building code, each gas supply connector shall be listed for outside manufactured home use, shall be not more than 6 feet (1829 mm) in length, and shall have a capacity rating to supply the connected load. [NFPA 501A:4.4.1]
Upcodes Diagrams
Related Code Sections
E 404.1 Manufactured/Mobile Home Parks and Recreational Vehicle Parks, Flexible Gas Connector
in accordance with the local building code or, in the absence of a local code, with a recognized model building code, each gas supply connector shall be listed ...
1208.7.2 Fuel Gas Piping, Supports
Gas meters shall be supported or connected to rigid piping so as not to exert a strain on the meters. Where flexible connectors are used to connect ...
1212.5.3 Fuel Gas Piping, Flexible Connectors
or thermal damage and shall be provided with gas shutoff valves in readily accessible locations in rigid piping upstream from the flexible connections ...
1323.6.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Flexible Connectors
Flexible connectors, metallic or nonmetallic, shall have a minimum burst pressure, with a gauge pressure of 1000 psi (6895 kPa). [NFPA 99 ...
604.5 Water Supply and Distribution, Flexible Connectors
Flexible water connectors shall be installed in readily accessible locations, and where under continuous pressure shall comply with ASME A112.18.6 ...