Flexible cords shall comply with the following:
  1. Be of a type listed for extra-hard usage
  2. Contain, in addition to the conductors of the circuit, an equipment grounding conductor complying with 400.23
  3. Be supported by clamps or other suitable means in such a manner that there will be no tension on the terminal connections
  4. Be terminated with a listed dusttight cord connector