603.6 Flexible Air Ducts and Flexible Air Connectors
JUMP TO FULL CODE CHAPTER
Flexible air ducts, both metallic and nonmetallic, shall be tested in accordance with UL 181. Such ducts shall be listed and labeled as Class 0 or Class 1 flexible air ducts and shall be installed in accordance with Section 304.1.
Flexible air ducts shall not be limited in length.
Flexible air connectors, both metallic and nonmetallic, shall be tested in accordance with UL 181. Such connectors shall be listed and labeled as Class 0 or Class 1 flexible air connectors and shall be installed in accordance with Section 304.1.
Flexible air connectors shall be limited in length to 14 feet (4267 mm).
Flexible air connectors shall not pass through any wall, floor or ceiling.
The design temperature of air to be conveyed in flexible air ducts and flexible air connectors shall be less than 250°F (121°C).
Related Code Sections
603.6 Duct Systems, Flexible Air Ducts and Flexible Air Connectors
Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4. Flexible air connectors, both ...
Mechanical Code 2021 of Colorado > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors
603.6 Duct Systems, Flexible Air Ducts and Flexible Air Connectors
Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4. Flexible air connectors, both ...
Mechanical Code 2015 of Colorado > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors
603.6 Duct Systems, Flexible Air Ducts and Flexible Air Connectors
Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4. Flexible air connectors, both ...
Mechanical Code 2018 of Colorado > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors
603.6.2 Duct Systems, Flexible Air Connectors
Flexible air connectors, both metallic and nonmetallic, shall be tested in accordance with UL 181. Such connectors shall be listed and labeled ...
Mechanical Code 2018 of Colorado > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors > 603.6.2 Flexible Air Connectors
603.6.1 Duct Systems, Flexible Air Ducts
Flexible air ducts, both metallic and nonmetallic, shall be tested in accordance with UL 181. Such ducts shall be listed and labeled as Class 0 ...
Mechanical Code 2021 of Colorado > 6 Duct Systems > 603 Duct Construction and Installation > 603.6 Flexible Air Ducts and Flexible Air Connectors > 603.6.1 Flexible Air Ducts