// CODE SNIPPET
606.12.5 Flaring Systems
JUMP TO FULL CODE CHAPTER
Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant incineration shall not pose health or environmental hazards. Incineration shall be automatic upon initiation of discharge, shall be designed to prevent blowback and shall not expose structures or materials to threat of fire. Standby fuel, such as LP gas, and standby power shall have the capacity to operate for one and one-half the required time for complete incineration of refrigerant in the system.
Related Code Sections
605.12.6 Building Services and Systems, Flaring Systems
Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant ...
2020 Minnesota State Fire Code > 6 Building Services and Systems > 605 Mechanical Refrigeration > 605.12 Discharge and Termination of Pressure Relief and Purge Systems > 605.12.6 Flaring Systems
606.12.5 Building Services and Systems, Flaring Systems
Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant ...
Minnesota Fire Code 2015 > 6 Building Services and Systems > 606 Mechanical Refrigeration > 606.12 Termination of Relief Devices > 606.12.5 Flaring Systems
Section 1109 Refrigeration, Periodic Testing
by the code official: Treatment and flaring systems. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes. Fans ...
Section 1109 Refrigeration, Periodic Testing
by the code official: Treatment and flaring systems. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes. Fans ...
1109.1 Refrigeration, Testing Required
by the code official: Treatment and flaring systems. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes. Fans ...