1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C)
JUMP TO FULL CODE CHAPTER
The storage of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) in connection with spraying operations shall conform to the requirements of 1910.106, where applicable.
The quantity of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) kept in the vicinity of spraying operations shall be the minimum required for operations and should ordinarily not exceed a supply for 1 day or one shift. Bulk storage of portable containers of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) shall be in a separate, constructed building detached from other important buildings or cut off in a standard manner.
Original closed containers, approved portable tanks, approved safety cans or a properly arranged system of piping shall be used for bringing flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) into spray finishing room. Open or glass containers shall not be used.
Except as provided in paragraph (e)(5) of this section the withdrawal of flammable liquids and liquids with a flashpoint greater than 199.4 °F (93 °C) from containers having a capacity of greater than 60 gallons shall be by approved pumps. The withdrawal of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) from containers and the filling of containers, including portable mixing tanks, shall be done only in a suitable mixing room or in a spraying area when the ventilating system is in operation. Adequate precautions shall be taken to protect against liquid spillage and sources of ignition.
Containers supplying spray nozzles shall be of closed type or provided with metal covers kept closed. Containers not resting on floors shall be on metal supports or suspended by wire cables. Containers supplying spray nozzles by gravity flow shall not exceed 10 gallons capacity. Original shipping containers shall not be subject to air pressure for supplying spray nozzles. Containers under air pressure supplying spray nozzles shall be of limited capacity, not exceeding that necessary for 1 day's operation; shall be designed and approved for such use; shall be provided with a visible pressure gage; and shall be provided with a relief valve set to operate in conformance with the requirements of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel Code - 1968, which is incorporated by reference as specified in Sec. 1910.6. Containers under air pressure supplying spray nozzles, air-storage tanks and coolers shall conform to the standards of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel Code - 1968 for construction, tests, and maintenance.
All containers or piping to which is attached a hose or flexible connection shall be provided with a shutoff valve at the connection. Such valves shall be kept shut when spraying operations are not being conducted.
All pressure hose and couplings shall be inspected at regular intervals appropriate to this service. The hose and couplings shall be tested with the hose extended, and using the "inservice maximum operating pressures." Any hose showing material deteriorations, signs of leakage, or weakness in its carcass or at the couplings, shall be withdrawn from service and repaired or discarded.
Piping systems conveying flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) shall be of steel or other material having comparable properties of resistance to heat and physical damage. Piping systems shall be properly bonded and grounded.
When a pump is used to deliver products, automatic means shall be provided to prevent pressure in excess of the design working pressure of accessories, piping, and hose.
Electrically powered spray liquid heaters shall be approved and listed for the specific location in which used (see paragraph (c) of this section). Heaters shall not be located in spray booths nor other locations subject to the accumulation of deposits or combustible residue. If an electric motor is used, see paragraph (c) of this section.
If flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) are supplied to spray nozzles by positive displacement pumps, the pump discharge line shall be provided with an approved relief valve discharging to a pump suction or a safe detached location, or a device provided to stop the prime mover if the discharge pressure exceeds the safe operating pressure of the system.
Whenever flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) are transferred from one container to another, both containers shall be effectively bonded and grounded to prevent discharge sparks of static electricity.
Related Code Sections
1910.107(e) Hazardous Materials, Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C)
The storage of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) in connection with spraying operations shall conform ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C)
1910.107(e)(8) Hazardous Materials, Pump Relief
If flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) are supplied to spray nozzles by positive displacement pumps ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C) > 1910.107(e)(8) Pump Relief
1910.107(e)(7) Hazardous Materials, Spray Liquid Heaters
Electrically powered spray liquid heaters shall be approved and listed for the specific location in which used (see paragraph (c) of this section ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C) > 1910.107(e)(7) Spray Liquid Heaters
1910.107(e)(6) Hazardous Materials, Pipes and Hoses
Piping systems conveying flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C) > 1910.107(e)(6) Pipes and Hoses
1910.107(e)(5) Hazardous Materials, Spraying Containers
Containers supplying spray nozzles shall be of closed type or provided with metal covers kept closed. Containers not resting on floors shall ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C) > 1910.107(e)(5) Spraying Containers