3504.1.3 Flammable Gas Storage of 3,500 SCF (99.12 M3) or Less
JUMP TO FULL CODE CHAPTER
Indoor storage shall be protected against damage or injury from falling objects or surrounding activity, and be located not less than:
- 20 feet (6096 mm) from all classes of flammable and combustible liquids, oxidizing gases and readily combustible materials, such as paper and combustible fibers.
- 25 feet (7620 mm) from open flames, ordinary electrical equipment or other sources of ignition.
- 50 feet (15 240 mm) from air-conditioning equipment, air compressors and intakes of ventilation.
- 50 feet (15 240 mm) from other flammable gas storage.
Related Code Sections
307.1 Use and Occupancy Classification, High-Hazard Group H
-OPEN SYSTEMS d
Solid pounds e,f
Liquid gallons (pounds) e,f
Gas, SCF e (standard cubic foot)$
Solid pounds e ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.1 High-Hazard Group H
307.1 Use and Occupancy Classification, High-Hazard Group H
quantities, except for liquefied petroleum gas and flammable liquid motor fuel, shall be increased 100 percent when stored in approved storage ...
NYC Building Code 2014 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.1 High-Hazard Group H
908.9 Fire Protection Systems, Flammable Gas
Areas within buildings containing flammable gas distribution piping operating at levels above 15 pounds per square inch gauge (psig) (103.4 kPa ...
NYC Building Code 2008 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.9 Flammable Gas
908.9 Fire Protection Systems, Flammable Gas
Rooms and spaces containing flammable gas distribution piping operating at levels above 15 pounds per square inch gauge (psig) (103.4 kPa) shall ...
NYC Building Code 2014 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.9 Flammable Gas
415.9.2.1.1 Special Detailed Requirements Based on Use and Occupancy, Aggregate Quantities
SOLIDS (pounds per square feet)
LIQUIDS (gallons per square feet)
GAS SCF/square feet)
PHYSICAL-HAZARD MATERIALS ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.9 Group H-5 > 415.9.2 Fabrication Areas > 415.9.2.1 Hazardous Materials in Fabrication Areas > 415.9.2.1.1 Aggregate Quantities