// CODE SNIPPET

Section 909 Fixture Vents

Plumbing Code 2015 of Utah > 9 Vents > 909 Fixture Vents
JUMP TO FULL CODE CHAPTER

909.1 Distance of Trap From Vent

Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in Table 909.1.

Exception: The developed length of the fixture drain from the trap weir to the vent fitting for self-siphoning fixtures, such as water closets, shall not be limited.

TABLE 909.1 MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT

SIZE OF TRAP
(inches)
SLOPE
(inch per foot)
DISTANCE FROM TRAP
(feet)
11/4 1/4 5
11/2 1/4 6
2 1/4 8
3 1/8 12
4 1/8 16

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 inch per foot = 83.3 mm/m.

909.2 Venting of Fixture Drains

The total fall in a fixture drain due to pipe slope shall not exceed the diameter of the fixture drain, nor shall the vent connection to a fixture drain, except for water closets, be below the weir of the trap.

909.3 Crown Vent

A vent shall not be installed within two pipe diameters of the trap weir.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 909 Vents, Fixture Vents
Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir ...
Plumbing Code 2018 of Utah > 9 Vents > 909 Fixture Vents
Section 909 Vents, Fixture Vents
Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir ...
Plumbing Code 2015 of Utah > 9 Vents > 909 Fixture Vents
Section P3105 Vents, Fixture Vents
Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir ...
Residential Code 2015 of Utah > 31 Vents > P3105 Fixture Vents
909.2 Vents, Venting of Fixture Drains
The total fall in a fixture drain due to pipe slope shall not exceed the diameter of the fixture drain , nor shall the vent connection ...
Plumbing Code 2015 of Utah > 9 Vents > 909 Fixture Vents > 909.2 Venting of Fixture Drains
909.3 Vents, Crown vent
A vent shall not be installed within two pipe diameters of the trap weir ...
Plumbing Code 2018 of Utah > 9 Vents > 909 Fixture Vents > 909.3 Crown vent
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US